DF-60957:A • 1/8/2018 — Page 1 of 4
ES-200X
Intelligent Addressable FACP
with Communicator
Addressable Fire Alarm Control Panels
DF-60957:A
General
The ES-200X is the latest intelligent addressable Fire Alarm Control
Panel (FACP) from Fire•Lite Alarms. The ES-200X comes with a
pre-installed communicator and supports up to 198 addressable
devices (99 detectors and 99 modules). With an extensive list of
powerful features, the ES-200X programs just like Fire•Lite’s other
addressable products, yet fits into applications previously served
only by conventional panels.
The pre-installed IPOTS-COM is a dual technology (POTS and IP)
communicator. The POTS transmits system status (alarms, troubles,
AC loss, etc.) to a Central Station via the public switched telephone
network. The IP communicator’s internet monitoring capability sends
alarm signals over the Internet saving the monthly cost of two dedi-
cated business telephone lines. Although not required, the second-
ary telephone line may be retained providing backup communication
over the public switched telephone line. Optional cellular reporting is
available using the CELL-MOD or CELL-CAB-FL.
Remote and local programming of the control panel is possible using
the FS-Tools Upload/Download utility. Programming databases can
be uploaded/downloaded via the panel’s USB port (and USB cable)
or via an ethernet connection using the IPOTS-COM communicator.
The USB port also allows for the download or upload of the entire
program, history file, walk-test data, current status and system volt-
ages by means of a USB flash drive.
The power supply and all electronics are contained on a circuit
board supported on a new quick install chassis and housed in a
metal cabinet. Available accessories include local and remote
upload/download software, remote annunciators, and reverse polar-
ity/city box transmitter (4XTMF).
Features
Listed to UL Standard 864, 10th edition
Pre-installed IPOTS-COM Ethernet IP and POTS (Plain Old Tele-
phone Service) Central Station Communicator over AlarmNet
Optional CELL-MOD or CELL-CAB-FL GSM Central Station
Communicator over AlarmNet®
Automated activation of the ECC-50/100 Emergency Command
Center
ECC-FFT Firefighter Telephone option
Compatible with SWIFT® wireless devices
Auto-programming (learn mode) reduces installation time.
Reports two devices set to the same address
Four built-in, independently programmable Style Z (Class A) or
Style Y (Class B) NAC circuits
Selectable strobe synchronization for System Sensor, Wheelock,
and Gentex devices
Notification Appliance Circuit End of Line resistor matching
Four programmable function keys for ease of maintenance
Two programmable relays and one fixed trouble relay
Built-in Programmer
Integral 80-character LCD display with backlighting
Real-time clock/calendar with automatic daylight savings control
History file with 1,000 event capacity
Addressable sounder base compatibility
Multi-criteria detector (smoke, heat, CO) with programmable
response
Control module delay timer
Automatic detector sensitivity testing (NFPA 72 compliant)
Automatic device type-code verification
Point trouble identification
Waterflow selection per module point
Alarm verification selection per detector point
Maintenance alert warns when smoke detector dust accumula-
tion is excessive
One-person audible or silent walk test with walk-test log and
printout
System alarm verification selection per detector point
PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA
72 compliant)
Up to 16 ANN-BUS annunciators- 8 per each ANN-Bus
Remote Acknowledge, Alarm Silence, Reset and Drill via
addressable modules or remote annunciator
Upload/Download of program and data via USB with optional FS-
Tools Programming Utility
SLC COMMUNICATION LOOP
Supports LiteSpeed™ and CLIP protocols
SLC operates up to 10,000 ft. (3,000 m) in LiteSpeed mode with
twisted, unshielded wire
Single addressable SLC loop which meets NFPA Class B and
Class A requirements
198 addressable device capacity (99 addressable detectors and
99 modules)
Compatible with Fire•Lite’s addressable devices (refer to the
SLC Wiring Manual)
NOTIFICATION APPLIANCE CIRCUITS (NACS)
Two independently programmable output circuits. Circuits can be
configured for the following outputs:
–Style Y (Class B)
–Style Z (Class A)
Silence Inhibit and Autosilence timer options
Continuous, March Time, Temporal, or California code for main
circuit board NACs with two-stage capability
Selectable strobe synchronization per NAC
2.5 A special application, 250mA regulated, total power for NACs
NOTE: Maximum or total 24VDC system power shared between all NAC
circuits and the ANN-BUS is 2.7 A
Whitney Even on 06/22/2022

Other manuals for Honeywell Fire-Lite Alarms ES-200X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Fire-Lite Alarms ES-200X and is the answer not in the manual?

Honeywell Fire-Lite Alarms ES-200X Specifications

General IconGeneral
TypeFire Alarm Control Panel
Output Voltage24VDC
Operating Temperature32°F to 120°F (0°C to 49°C)
CompatibilityCompatible with Fire-Lite devices
NAC Circuits4
Power Supply120 VAC, 60 Hz
Battery Charging Current1.0 A
Dimensions14.5" x 12" x 3.5"
Relative Humidity93% RH noncondensing
Power120 VAC, 60 Hz