FL-PS Series Instruction Manual P/N LS10227-001FL-E:B 3/29/2021 29
Section 4: LED Indicators
The FL-PS power supply has 3 system LED indicators for Power, Batt/Chgr Fault, and Ground Fault. In addition, each available output
circuit also has 2 status LEDs. Refer to Figure 1.1 on page 10 for LED locations. A description of each FL-PS LED indication is given
below.
Ground Fault LED (yellow)
No Fault LED is OFF
Fault Condition:
ground fault
LED is ON constant
Power LED (green)
No Fault LED is ON constant
Fault Condition:
AC power loss (or brownout)
1 short blink (250ms)
Repeating LED blink pattern (non-diagnostic mode and diagnostic mode)
Battery fault LED (yellow)
No Fault LED is OFF
Fault Condition:
Charging path (FETs) failure
1 short blink (250ms)
Repeating LED blink pattern (non-diagnostic mode and diagnostic mode)
Fault Condition:
Charger voltage too low or
Charger Diode Fault
2 short blinks (250ms)
Repeating LED blink pattern (non-diagnostic mode and diagnostic mode)
Fault Condition:
Battery discharged/overcharged
3 short blinks (250ms)
Repeating LED blink pattern (non-diagnostic mode and diagnostic mode)
Fault Condition:
Battery disconnected/fully
discharged
4 short blinks (250ms)
Repeating LED blink pattern (non-diagnostic mode and diagnostic mode)
250ms
250ms
250ms
250ms
250ms
250ms
250ms
250ms
1000ms
pause
250ms
250ms
250ms
250ms
250ms
250ms
250ms
250ms
1000ms
pause
250ms
250ms
250ms
250ms
250ms
250ms
250ms
250ms
1000ms
pause
250ms
250ms
250ms
250ms
250ms
250ms
250ms
250ms
1000ms
pause
250ms
250ms
250ms
250ms
250ms
250ms
250ms
250ms
1000ms
pause

Table of Contents

Related product manuals