FL-PS Series Instruction Manual P/N LS10227-001FL-E:B 3/29/2021 43
Canadian Two-Stage Application Examples
B.7 Canadian Two-Stage
In this application, NAC1 from the Host FACP is providing the Canada 2-stage audible pattern to the FL-PS and NAC. NAC2 is provid-
ing Master Sync or a Steady Output, depending on its capabilities.
The following notes apply to Figure B.7.
FL-PS Output #1 is programmed to activate on Command Input #1 and slave mode (NAC follower).
FL-PS Output #2 is programmed depending on the host FACP capabilities.
FACP NAC2 provides master sync: FL-PS Output #2 activate on Command Input 2, slave mode (NAC follower)
FACP NAC2 provides steady output: FL-PS Output #2 activate Command Input 2, master mode (select appropriate strobe
manufacturer)
Additional FL-PS outputs can be mapped to command inputs and used to drive additional visual/audible or FL-PS units.
AC1 AC2
T
B
4
TB15
T
B
3
T
B
2
T
B
1
O
U
T
6
O
U
T
5
O
U
T
4
O
U
T
3
O
U
T
2
O
U
T
1
+
+
-
-
+
-
+
-
+
+
-
-
+
-
+
-
Host FACP
NAC1
NAC2
horn circuitstrobe circuit
Figure B.7 Canadian Two-Stage Wiring