42 FL-PS Series Instruction Manual — P/N LS10227-001FL-E:B 3/29/2021
Application Examples AC Trouble Reporting with a Conventional FACP
B.6 AC Trouble Reporting with a Conventional FACP
In this application, the FL-PS is being used with a conventional FACP that does not have a type-coded input zone for AC Power loss
with a delay. AC Trouble Delay on the FL-PS must be set to none (S1-7 ON, 8 ON). AC Fail delay timers must be set on the DACT. The
DACT must be installed in close proximity to the conventional FACP so the audible and visual signaling can be given locally at the
FACP as required by UL 864.
The following notes apply to Figure B.6.
Wiring from the power supply to the DACT must be in metal conduit within 20 feet of the FACP.
Refer to Section 3 for instructions on setting the DIP switches.
Do not loop wires under screw terminals. Break wires to maintain proper supervision.
An End-of-Line Resistor must be installed between terminals 1 and 4 on the input circuits that require wiring supervision. (The
ELR value is dependent on the FACP employed).
Refer to panel/DACT documentation for programming information.
NO NC C NO NC C
TB4
TB15
T
B
2
T
B
1
T
B
1
3
O
U
T
6
T
B
1
2
O
U
T
5
T
B
1
1
O
U
T
4
T
B
1
0
O
U
T
3
T
B
9
O
U
T
2
T
B
8
O
U
T
1
AC1 AC2
TB1
TB2
B+ B- B+ B-
NAC 1 NAC 2
+ - + -
Nonreset
Reset
B+ B- B+ B-
ZONE 1 ZONE 2
B+ B- B+ B-
ZONE 3 ZONE 4
C NO NC C NC NO
C NC NO
TROUBLE ALARM SUPV
UL 864 Listed Regulated 24 VDC
Conventional FACP
UL 864
10th Edition
Listed DACT
Channel 1
Channel 2
Channel 3
Channel 4
NAC
+ -
24VDC non-resettable power
+ -
FL-PS
ELR
ELR
ELRs
Figure B.6 AC Trouble Reporting with a Conventional FACP