LCD-SLP Product Installation Document — P/N LS10045-000GF-E:E 12/16/2019 13
Section 4: LCD-SLP Display Panel
4.1 LCD-SLP Touchscreen LEDs and Switches
Figure 4.1.1 illustrates the screen that appears when you program in CAMWorks for Non-Releasing Fire applications.
Table 4.1.1 lists the LCD-SLP, LED indicators, Audible/Visual Status indicators and the switches.
.
Figure 4.1.1 LCD-SLP Non-Releasing Fire Touchscreen LEDs and Switches
LCD-SLP LED Indicators
Designation Description Description
AC Power GREEN Lights to indicate the presence of AC voltage input.
Fire Alarm RED Lights when the system is in alarm, flashes until the alarm is acknowledged.
Hazard BLUE Lights to indicate a hazard condition, flashes until it is acknowledged.
Supervisory YELLOW Lights when a supervisory condition exists, flashes until the trouble acknowledge is
performed.
Trouble YELLOW Lights to indicate a trouble condition, flashes until the trouble is acknowledged.
Silenced YELLOW Lights when the System Silence is pressed.
Flashes when the System Silence is pending.
LCD-SLP Audible/Visual Condition Indicators
Condition Audible/Visual Status Indicators
Alarm Alarm situations are indicated by a one-half second ON and one-half second OFF
pattern from the system sounder & the illumination of the red alarm LED.
Hazard Hazard situations are reported by a Coded 4 pattern.
Supervisory Supervisory events are indicated by a continuous tone from the system piezo sounder
and the illumination of the supervisory LED.
Trouble Trouble conditions are indicated by a continuous tone from the system piezo sounder
and the illumination of the YELLOW trouble LED.
LCD-SLP Non-Releasing Fire Switches
Switch Description
Menu Toggles the Menu ON and OFF. (See Notes 1 and 2)
Drill Initiates a fire drill. (See Note 1 and 2)
Reset Initiates a System Reset, as well as five User-Defined switches.
User-Defined Switches Custom indication & switch function. This switch must be programmed in CAMWorks.
(See Note 1)
NOTES
Note 1: The Menu, Drill and User-Defined switches are not available on Releasing displays.
Note 2: The Menu and Drill switches are not available when the Releasing Zone to which the LCD-SLP belongs is
OFF-NORMAL.
Table 4.1.1 LCD-SLP LED Indicators, Audible/Visual Indicators and Switches
FIRE ALARM HAZARD SUPERVISORY TROUBLE
AC POWER
SILENCED
MENU DRILL RESET