Specifications Product Description
The following figure illustrates the maximum current that is possible for each major panel output circuit and the total current available
from the FACP with the FLPS-7 power supply. This applies to the GF505 & GF510.
TB9
TB5
TB7
TB3
TB1
Figure 1.1 Current Availability with FACP and FLPS-7 Power Supply
powerdistmrp.wmf
Refer to the battery calculations section for additional information.
Standby
1.0 amp max
per panel
Special Application
Nonresettable or
Resettable Power
Special Application
Resettable Power
NAC #1
NAC #2
NAC #3
NAC #4
0.5 amp max
per circuit
0.5 amp max
per circuit
3.0 amps max
per circuit
3.0 amps max
per circuit
3.0 amps max
per circuit
3.0 amps max
per circuit
Alarm
7.0 amps max
per panel
Primary
ANN-BUS
Standby
1.0 amp max
per panel
0.5 amp max
per circuit
0.5 amp max
per circuit
ANN-SEC
Option Card
GF505 & GF510 Manual P/N 53164:B5 6/12/2018
15