EasyManuals Logo

Honeywell GF505 User Manual

Honeywell GF505
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #37 background imageLoading...
Page #37 background image
ANN-BUS Devices Installation
2.8.3 GFANN-80 Remote Fire Annunciator
The GFANN-80 Annunciator is a compact, 80 character, backlit LCD remote fire annunciator which mimics the FACP display. It also
provides system status indicators for AC Power, Alarm, Trouble, Supervisory and Alarm Silenced conditions. The GFANN-80 Annunci-
ator provides buttons for remote Reset, Silence, Acknowledge, and Drill of the FACP. Communication between the GFANN-80 and
FACP is accomplished over a two wire serial interface employing the ANN-BUS communication format. The devices are powered, via
two additional wires, from either the host FACP or remote UL-listed, filtered, power supply.
Specifications
Operating Voltage Range: 18 VDC to 28 VDC
Current Consumption @ 24 VDC nominal (filtered and nonresettable):
Normal/Standby (no activity): 37.0 mA
Trouble: 39.0 mA
Alarm: 40.0 mA
AC Fail ( not backlit): 15.0 mA
For use indoors in a dry location
Installation
Ensure that all power (AC and DC) has been removed from the FACP before installing the annunciator.
Opening/Closing Annunciator
The following procedure details the steps used to open the annunciator in order to access the terminal block and DIP switches (refer to
figure below):
1. Turn the key switch to the ON (Unlocked) position by turning the key counter-clockwise
2. Push in the snap latch located on the right side of the unit while pulling the cover open
3. To close the cover, make certain the key switch is in the ON (Unlocked) position. Swing the cover closed, snapping it shut
4. Turn the key switch to the OFF (Locked) position by turning clockwise and remove the key
Mounting
The GFANN-80 can be surface or semi-flush mounted to a single, double or 4” square electrical box. Select and remove the appropriate
knockout(s), pull the necessary wires through the knockouts and mount the annunciator in or on the wall depending on the type of instal-
lation desired.
The ANN-SB80KIT(-R/-B/-W) is an available mounting kit for the ANN-80 annunciator. The kit comes with a surface backbox and sur-
face wedge for angled viewing. The two pieces can be used separately or can be stacked together.
Key switch shown
in ON position
Press in latch
and
Pull annunciator
cover open
Annunciator cover
with LCD display
Annunciator backplate
ann-80_iso.wmf
GF505 & GF510 Manual P/N 53164:B5 6/12/2018
37

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell GF505 and is the answer not in the manual?

Honeywell GF505 Specifications

General IconGeneral
BrandHoneywell
ModelGF505
CategoryControl Panel
LanguageEnglish

Related product manuals