EasyManua.ls Logo

Honeywell HPF24S6 - DIP Switch Settings

Honeywell HPF24S6
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20 HPF24S Series Power Supplies — P/N 52751:E1 4/14/2011
Programming Options DIP Switch Settings
3.1 DIP Switch Settings
The following table lists the HPF24S programmable features and the switch settings required to
select a particular feature. A detailed description of each feature is presented in the following
pages.
SW1 DIP Switch ON OFF
1 This switch works in conjunction with switch 2 to determine the Strobe Synchronization Type
1
.
2 1 OFF, 2 OFF = no sync (steady +24V) - default
1 OFF, 2 ON = System Sensor
1 ON, 2 OFF = Gentex
1 ON, 2 ON = Wheelock
3 FCPS configured for Slave Synchronization FCPS configured for Master Synchronization - default
4 Delay AC Fail Reporting for 2 Hours - default
Aux. Trouble Relay responds to all troubles
Internal Trouble contact responds to AC loss
No Delay in AC Fail Reporting
Aux. Trouble Relay responds only to AC Fail/Brownout
Internal Trouble contact does not respond to AC loss
5 This switch works in conjunction with switch 6 to determine Input to Output functions
6 5 OFF, 6 OFF = General Alarm - default
FCPS configured as Master (switch 3 OFF), NAC Outputs 1 through 4
2
are controlled by Control Input #1;
Sync Input is ignored.
FCPS configured as Slave (switch 3 ON), NAC Outputs 1 through 4
2
are controlled by Control Input #1;
Sync Input is monitored
3
.
Resettable or nonresettable Auxiliary Power Output is available from TB4 Terminals 9 & 10. Control Input
#2 determines if reset will occur (must go from On to Off for a minimum 6 second reset to occur).
Output #4 function follows DIP switch 8 setting.
5 OFF, 6 ON = Split Alarm
FCPS configured as Master (switch 3 OFF), NAC Outputs 1 & 2 are controlled by Control Input #1 and
Outputs 3 & 4
2
are controlled by Control Input #2; Sync Input is ignored.
FCPS configured as Slave
4
(switch 3 ON), NAC Outputs 1 & 2 are controlled by Control Input #1 and
Outputs 3 & 4
2
are controlled by Control Input #2; Sync Input is monitored
3
.
Only nonresettable Auxiliary Power is available from TB4 Terminals 9 & 10.
Output #4 function follows DIP switch 8 setting.
5 ON, 6 OFF = Split Temporal
FCPS configured as Master (switch 3 OFF), Control Input #1 controls NAC Outputs 1 & 2 and Control Input
#2 controls Outputs 3 & 4
2
which will generate a Temporal code signal without sync; Sync Input is ignored.
FCPS configured as Slave (switch 3 ON), Control Input #1 controls NAC Outputs 1 & 2 and Control Input #2
controls Outputs 3 & 4
2
which will generate a Temporal code signal without sync; Sync Input is monitored
for Outputs 1 & 2
3
.
Only nonresettable Auxiliary Power is available from TB4 Terminals 9 & 10.
Output #4 function follows DIP switch 8 setting.
5 ON, 6 ON = Selective Silence
FCPS configured as Master (switch 3 OFF), NAC Outputs 1 through 4
2
are controlled by Control Input #1;
Sync Input is ignored.
Control Input #2 determines when Selective Silence for all outputs will occur
5
Only nonresettable Auxiliary Power is available from TB4 Terminals 9 & 10.
Output #4 function follows DIP switch 8 setting.
7 Disable Charger Enable Charger - default
8 Output Circuit #4 = Door Holder Output Circuit #4 = NAC - default
Table 3.1 DIP Switch Settings
1 Strobe Synchronization only works with non-coded NACs.
2 If Door Closer function is selected (switch 8 ON), Output 4 does not function as an NAC, therefore sync input is
ignored for it.
3If no synchronization is selected by switches 1 & 2, the Sync Input is ignored.
4 When using Split Alarm with power supply configured for Slave Mode, System Sensor cannot be used (use
System Sensor with Master Mode only).
5 Selective Silence allows the silencing of the sounder portion of a horn/strobe combination device without turning
off the strobe.

Table of Contents

Related product manuals