36 HPF24S Series Power Supplies — P/N 52751:E1 4/14/2011
Applications Master HPF24S Power Supply Connected to FACP
5.6 Master HPF24S Power Supply Connected to FACP
In this application, a master HPF24S power supply, set for synchronization, is connected to an
FACP with nonsynchronized output.
The following notes apply to this illustration
1. Refer to NFPA 72, Chapter 4-4, Visible Characteristics, Public Mode.
2. Use only devices from the same manufacturer in each system.
5.7 Canadian Applications
Canadian applications, per ULC, require the following:
The HPF24S power supply must be used as a Notification Appliance Circuit extender only.
The TB2 terminals cannot be configured as auxiliary power outputs.
The host FACP must monitor for all ground fault conditions. The Ground Fault Detection
circuit on the HPF24S power supply must be disabled by cutting jumper JP1.
-
+
TB4
JP3
J3
TB5
TB2
JP1
JP2
OUT4
-NAC4+
OUT3
-NAC3+
OUT2
-NAC2+
OUT1
-NAC1+
AUX -
IN2-
IN2+
OUT1-
OUT1+
IN1-
IN1+
SYNC IN -
SYNC IN +
AUX +
NO NC
AUX TBL
COM
1 2 3 4 5 6 7 8 9 10
8
7
6
5
4
3
2
1
3
2
1
Standby Polarity Shown
HPF24S
SW1 Switch Settings
1 & 2 = sync (any setting
but OFF/OFF)
3 = OFF (master)
4 = OFF (No AC Fail
Reporting Delay)
5 = OFF
6 = OFF
7 = OFF (charger enabled)
8 = OFF (circuit 4 NAC)
Figure 5.6 Supervised FACP to Master Connections (nonsynchronized source)
general alarm
24fsapp11b.wmf
FACP
NAC with no
syncronization
NAC1
Internal Trouble
Contact
ELR for
FACP
NAC