GB-6
Connection diagram for TC
 ▷
The tightness test is carried out with the auxiliary 
valves installed on TC 3 (pre-wired). The terminals 
for the valve inputs remain vacant.
Mains voltage and control voltage: 
24VDC/120VAC/230VAC
Mains voltage: 120VAC/230VAC, 
control voltage: 24VDC
Finishing the wiring
9
Tightness test
 ▷ All new connections between the valve and the 
TC must be checked for tightness.
    Pressurize the system. Do not exceed the maxi-
mum inlet pressure.
   Soap off pipe connections.
Setting the test instant
 ▷
The test instant (MODE) can be set using two 
DIP switches.
   Disconnect the unit from the electrical power 
supply.
 ▷
Before opening the unit, the fitter should ground 
himself.
   Unscrew the housing cover.
   Set the test instant to Mode 1, 2 or 3.
5s
 ▷ Mode 1: test before burner start-up with incom-
ing thermostat/start-up signalϑ (factory setting).
Mode 1
 ▷ Mode 2: test after burner run when the thermo-
stat/start-up signal ϑ drops and after switching 
on the mains voltage.
 ▷ The tightness test also starts after a reset.
Mode 2
 ▷
Mode 3: test with incoming thermostat/start-up 
signal ϑ before burner start-up and when the 
thermostat/start-up signal ϑ drops after burner 
run.
Mode 3
 ▷ Invalid switch setting: no function. The 
 LED 
is permanently red, see page8 (Assistance 
in the event of malfunction).
 ▷
Continue on page 7 (Setting measurement 
time tM).