GB-9
 ?  
 yellow and permanently lit?
 !  Safety interlock input signal is interrupted, no 
voltage at terminal 5. The tightness test is still 
being carried out. No enable signal is issued to 
the automatic burner control unit.
 •  Check safety interlocks.
 !  Fuse F2 defective.
 •  Replace fuse F2, see page9 (Replacing the 
fuse).
 ?  
 yellow and flashing?
 !  Permanent remote reset. The remote reset signal 
has been active for more than 10s.
 •  The warning signal is cancelled once the remote 
reset signal to terminal11 has been removed.
 ?  
 red and permanently lit?
 !  Incorrect jumper/DIP switch setting.
 •  Correct jumper and DIP switch setting, see 
pages 7 (Setting measurement time tM) 
and6 (Setting the test instant). Then press 
the reset button.
 !  Internal error.
 •  Remove the unit and return it to the manufacturer 
for inspection.
 ?  
 red and flashing?
 !  Too frequent burner start commands. The TC 
performs a fault lock-out. The start commands 
are limited to 5x in 15minutes.
 ▷
As long as this limit is not exceeded, another 
start-up attempt is possible after three further 
minutes. If a tightness test is completed, the 
counter which limits the number of start com-
mands is reset.
 •  Then press the reset button.
 !  Too many remote resets. More than 5resets 
have been conducted within the last 15minutes, 
either automatically or manually.
 !  Consecutive fault caused by a previous fault 
whose actual cause has not been remedied.
 •  Pay attention to previous fault messages.
 •  Remedy cause. Then press the reset button.
 ?  
 or 
 red and permanently lit?
 !  The valve is leaking. The TC performs a fault 
lock-out.
 •  Replace the valve.
 !  Wiring of the TC to the valves is faulty.
 •  Start the program and observe the interspace 
pressurep
z
. The pressure must change during 
the TEST phase. Check the wiring.
 !  Inlet pressurep
u
 <10mbar.
 •  Provide the min. inlet pressure of 10mbar.
 !  Interspace pressurep
z
 cannot be reduced.
 •  The volume downstream of the valve on the 
burner side must be 5times higher than the 
volume between the valves and atmospheric 
pressure must prevail.
 !  The measurement time t
M
 is too long.
 •  Readjust t
M
, see page 7 (Setting measure-
ment time tM).
 ?  
 and 
 red and permanently lit?
 !  During the tightness test, the TC has determined 
that inlet valve1 and outlet valve2 have been 
reversed (fault lock-out).
 •  Check the wiring. Then press the reset button.
 ?  No LED lit even though mains voltage ap-
plied?
 !  Fuse F1 defective.
 •  Replace fuse F1, see page9 (Replacing the 
fuse).
Replacing the fuse
 ▷
The fuses F1 and F2 can be removed for in-
spection.
 ▷ Insert a screwdriver into the opening in the con-
tact guard to prise out the fuse.
   Disconnect the TC from the electrical power 
supply.
 ▷
Before opening the unit, the fitter should ground 
himself.
   Unscrew the housing cover.
   Remove fuse F1 or F2.
 4  Check function of fuse.
 5  Replace the defective fuse.
 ▷
When replacing the fuse, use only the approved 
fuse type, see page10 (Technical data).
 ▷ Restart the TC, see page8 (Commissioning).
Maintenance
Tightness controls TC require little servicing. We rec-
ommend carrying out a function check once a year 
or twice a year in the case of biogas.