EasyManuals Logo

Honeywell Kromschroder TC 3 User Manual

Honeywell Kromschroder TC 3
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
GB-9
D
GB
F
NL
I
E
?
1
2
Power
yellow and permanently lit?
! Safety interlock input signal is interrupted, no
voltage at terminal 5. The tightness test is still
being carried out. No enable signal is issued to
the automatic burner control unit.
Check safety interlocks.
! Fuse F2 defective.
Replace fuse F2, see page9 (Replacing the
fuse).
?
1
2
Power
yellow and flashing?
! Permanent remote reset. The remote reset signal
has been active for more than 10s.
The warning signal is cancelled once the remote
reset signal to terminal11 has been removed.
?
1
2
Power
red and permanently lit?
! Incorrect jumper/DIP switch setting.
Correct jumper and DIP switch setting, see
pages 7 (Setting measurement time tM)
and6 (Setting the test instant). Then press
the reset button.
! Internal error.
Remove the unit and return it to the manufacturer
for inspection.
?
1
2
Power
red and flashing?
! Too frequent burner start commands. The TC
performs a fault lock-out. The start commands
are limited to 5x in 15minutes.
As long as this limit is not exceeded, another
start-up attempt is possible after three further
minutes. If a tightness test is completed, the
counter which limits the number of start com-
mands is reset.
Then press the reset button.
! Too many remote resets. More than 5resets
have been conducted within the last 15minutes,
either automatically or manually.
! Consecutive fault caused by a previous fault
whose actual cause has not been remedied.
Pay attention to previous fault messages.
Remedy cause. Then press the reset button.
?
1
2
Power
or
1
2
Power
red and permanently lit?
! The valve is leaking. The TC performs a fault
lock-out.
Replace the valve.
! Wiring of the TC to the valves is faulty.
Start the program and observe the interspace
pressurep
z
. The pressure must change during
the TEST phase. Check the wiring.
! Inlet pressurep
u
<10mbar.
Provide the min. inlet pressure of 10mbar.
! Interspace pressurep
z
cannot be reduced.
The volume downstream of the valve on the
burner side must be 5times higher than the
volume between the valves and atmospheric
pressure must prevail.
! The measurement time t
M
is too long.
Readjust t
M
, see page 7 (Setting measure-
ment time tM).
?
1
2
Power
and
1
2
Power
red and permanently lit?
! During the tightness test, the TC has determined
that inlet valve1 and outlet valve2 have been
reversed (fault lock-out).
Check the wiring. Then press the reset button.
? No LED lit even though mains voltage ap-
plied?
! Fuse F1 defective.
Replace fuse F1, see page9 (Replacing the
fuse).
Replacing the fuse
The fuses F1 and F2 can be removed for in-
spection.
Insert a screwdriver into the opening in the con-
tact guard to prise out the fuse.
Disconnect the TC from the electrical power
supply.
Before opening the unit, the fitter should ground
himself.
Unscrew the housing cover.
Remove fuse F1 or F2.
4 Check function of fuse.
5 Replace the defective fuse.
When replacing the fuse, use only the approved
fuse type, see page10 (Technical data).
Restart the TC, see page8 (Commissioning).
Maintenance
Tightness controls TC require little servicing. We rec-
ommend carrying out a function check once a year
or twice a year in the case of biogas.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Kromschroder TC 3 and is the answer not in the manual?

Honeywell Kromschroder TC 3 Specifications

General IconGeneral
BrandHoneywell
ModelKromschroder TC 3
CategoryControl Unit
LanguageEnglish

Related product manuals