GB-7
Setting measurement time t
M
 ▷
The measurement time t
M
 can be set with a 
jumper in increments of 5s to max. 30s.
 ▷ t
M
 is set to 30s at the factory.
M
5s
10s
15s
20s
25s
30s
 ▷
No jumper: no function. The 
 LED is perma-
nently red, see page 8 (Assistance in the 
event of malfunction).
 ▷
The longer the measurement timet
M
, the greater 
the sensitivity of the tightness control. The longer 
the measurement time, the smaller the leakage 
rate at which a safety shut-down/fault lock-out 
is triggered.
 ▷
For all CG versions, the measurement 
timet
M
must be set to 5s on TC1C.
 ▷ If no leakage rate is specified, we recommend 
the max. measurement time is set.
 ▷
Within the scope of the European Union, the 
maximum leakage rate Q
L
 is 0.1% of the maxi-
mum flow rate Q
max.
 [m
3
/h (n)].
 ▷ If a leakage rate is specified, find the measure-
ment timet
M
 from the following:
   Q
max.
 = max. flow rate [m
3
/h]
   Q
L
 = Q
max. 
[m
3
/h] x 0.1% = leakage rate [ l/h]
   p
u
 = inlet pressure [mbar]
   V
P
 = test volume [ l ], see page7 (Values for 
valve and pipe volume)
 ▷
The tightness control TC requires a minimum 
start rate in order to carry out tightness tests 
on slow opening valves:
   up to 5l (1.3gal) test volume V
P
= 5% of maxi-
mum flow rateQ
max.
, up to 12l (3.12gal) test 
volume V
P
= 10% of maximum flow rateQ
max.
.
   Determine measurement time t
M
.
 ▷ Measurement times t
M
 for V1 and V2:
t
M
 [s] =
2.5 x p
u
 [mbar] x V
P
  [ l ]
Q
L
  [ l /h]
 ▷
The entire test period is made up of the meas-
urement timest
M
 of both valves and the fixed 
opening timet
L
 of both valves together:
t
P
 [s] = 2 x t
L
 + 2 x t
M
Values for valve and pipe volume
L
V
P
 = V
V
 + L  x V
V
P
V1
V2
Valves
Valve 
volume 
V
V
 [ l ]
Nomi-
nal size
DN
Pipe  
volume V
R
 
[ l/m]
VG 10 0.01 10 0.1
VG 15 0.07 15 0.2
VG 20 0.12 20 0.3
VG 25 0.2 25 0.5
VG 40/VK 40 0.7 40 1.3
VG 50/VK 50 1.2 50 2
VG 65/VK 65 2 65 3.3
VG 80/VK 80 4 80 5
VG 100/VK 100 8.3 100 7.9
VK 125 13.6 125 12.3
VK 150 20 150 17.7
VK 200 42 200 31.4
VK 250 66 250 49
VAS 1 0.08
VAS 2 0.32
VAS 3 0.68
VAS 6 1.37
VAS 7 2.04
VAS 8 3.34
VAS 9 5.41
VCS 1 0.05
VCS 2 0.18
VCS 3 0.39
VCS 6 1.11
VCS 7 1.40
VCS 8 2.82
VCS 9 4.34
Calculation example:
   Q
max.
 = 100 m
3
/h 
 p
u
 = 100 mbar 
 V
P
 = V
V
 + L x V
R
 = 7 l 
 Q
L
 = 100 m
3
/h x 0.1% = 100 l/h
2.5 x 100 x 7
 
= 17.5 s
100
   Set the next highest value (in this example 20s) 
with the jumper.
   Disconnect the unit from the electrical power 
supply.
   Unscrew the housing cover.
 4  Set the jumper to the position for the required 
measurement time.
 5  Position the housing cover and screw tight.
 6  Mark the set measurement timet
M
 on the type 
label with a waterproof pen.
TC
D-49018 Osnabrück, Germany
t
M
(s)  5 10 15 20 25 30
 ▷ The entire test period for this example is as fol-
lows: 2 x 3 s + 2 x 20 s = 46 s.