30 FCPS-24S Series Instruction Manual — P/N 51977:J2 7/11/2014
Applications Controlling Three NACs and One Door Holder With One Input
5. Supervise the power wiring between the FCPS-24S auxiliary 24 VDC output on TB4,
Terminals 9 & 10 with an EOL relay (P/N: EOLR-1).
6. For a list of compatible devices, refer to the Notifier Device Compatibility Document #15378.
7. IMPORTANT! When the power supply is programmed for both Selective Silence and Slave
Mode, TB4 Terminal 7 (IN+) must be jumpered to Terminal 9 (AUX+) and Terminal 8 (IN-)
must be jumpered to Terminal 10 (AUX-). The FACP will control the Selective Silence feature
with this configuration.
If the terminals are not jumpered as indicated, the horn portion of the horn/strobes will be
silenced
at all times.
5.2 Controlling Three NACs and One Door Holder With One
Input
In this application, the power supply has been set as a master with synchronized outputs. All four
FCPS-24S output circuits, three NACs and one door holder, can be controlled from one input such
as an addressable control module as illustrated in Figure 5.2. The control module can be powered
from the FCPS-24S auxiliary 24 VDC power output (TB4, Terminals 9 & 10).
TB4
1 2 3 4 5 6 7 8 9 10
SYNC SYNC IN+ IN- OUT+ OUT- IN2+ IN2- AUX+ AUX-

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER FCPS-24S8 and is the answer not in the manual?

Honeywell NOTIFIER FCPS-24S8 Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER FCPS-24S8
CategoryPower Supply
LanguageEnglish

Related product manuals