FCPS-24S Series Instruction Manual — P/N 51977:J2 7/11/2014 9
Start-up Procedure System Overview
Maximum current available for any one output circuit: 3.0 amps special application,
300mA regulated
Maximum total continuous current available:
4.0 amps for FCPS-24S6
6.0 amps for FCPS-24S8
Maximum total short term current (one hour maximum):
6.0 amps for FCPS-24S6
8.0 amps for FCPS-24S8
Integral supervised battery charger for lead acid batteries only
Capable of charging 7.0 AH to 18.0 AH (Amp Hour) batteries
Fully supervised power supply, battery and NACs
Selectable Strobe Synchronization for NACs (System Sensor, Gentex and Wheelock)
Coded signal synchronization
Fixed terminal blocks for field wiring capable of accepting 12 - 22 AWG wire
Selectable Ground Fault detection by jumper JP1
Power supply trouble Form-C relay contacts (fail-safe)
Optional delay of AC loss reporting for 2 hours
Auxiliary Special Application Power Output for SLC modules (500 mA maximum) with
optional reset for 4-wire smoke detectors
Mounting location for optional addressable control module
1.3 Start-up Procedure
1. Configure the power supply jumpers as described in “Jumpers” on page 10.
2. Install the power supply as described in“Installation” on page 14.
3. Program the power supply as described in “Programming Options” on page 20.
4. Wire the power supply circuits, referring to the options described in“Trouble Supervision” on
page 26 and the application examples in“Applications” on page 28.
5. Connect primary power source wiring while observing the following:
Make certain that the AC mains circuit breaker is off before making any wiring connections
between the mains and the power supply.
Make certain primary power source is 120 VAC, 60 Hz, 3.2 amps.
Run a pair of wires (with ground conductor) from the protected premises main breaker box
to TB1 of the power supply main circuit board.
Use 14 AWG (1.6 mm O.D.) or heavier gauge wire with 600V insulation.
6. Apply power to the power supply using the following procedure:
Apply AC power by turning on the AC mains circuit breaker connected to the power supply.
Connect a properly charged battery to connector JP4 on the power supply main circuit
board.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER FCPS-24S8 and is the answer not in the manual?

Honeywell NOTIFIER FCPS-24S8 Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER FCPS-24S8
CategoryPower Supply
LanguageEnglish

Related product manuals