NCA-2 Manual — P/N 52482:M5 03/20/2019 55
Security Access Programming
Figure 5.2 Change User Password
5.1.3 Unprotected Functions
Operators without a password can do basic tasks; if a key switch is installed on J6 and enabled, a key is required to enable the keypad.
The operator can perform the following keypad or menu-displayed functions:
Acknowledge alarms, troubles, and restorations (clears).
View acknowledged alarms and troubles.
Silence the sounding of fire alarm notification appliances.
Simultaneously reset all panels which are associated through programming.
Point Read Status for network devices and local NCA-2 annunciator points.
Test the NCA-2 LED indicators and Liquid Crystal Display (LCD).
View or print the event history stored in nonvolatile memory.
If the main operator of the system requires access to a function which is password protected, contact the Notifier distributor who
installed the system for the required password(s).
5.1.4 Key Switches
An AKS-1B Annunciator Key Switch is required for each NCA-2 unless the NCA-2 is installed in a lockable cabinet such as a CAB-4
series backbox. The AKS-1B is used to enable and disable the NCA-2 keypad. (see Section 3.16 “Annunciator Key Switch (AKS-1B)”).
In some jurisdictions, only one NCA-2 may have the keypad enabled at any given point in time; all other NCA-2 keypads must be dis-
abled using the AKS-1B If an NCS is installed on the network, each NCA-2 keypad must be disabled by enabling key switch monitoring
for the NCA-2 and locking the AKS-1B. A wiring diagram is provided in Section 3.16, “Annunciator Key Switch (AKS-1B)”, on page
33.
USER PASSWORD
LC
USER: 1 REFERENCE: Mary
ENTER PASSWORD: ********
RE-ENTER PASSWORD:
MODE: PROGRAM/ALTER STATUS ACCEPT
BACK
Main menu
Program/alter status menu
Panel program menu
Password change
User password
Enter user & mode
Enter password
Re-enter password
Passwords are
case sensitive.