NCA-2 Manual — P/N 52482:M5 03/20/2019 71
Panel Program Menu Programming
Regional Settings
Use the Regional Settings softkey to access the Regional Settings screen:
Figure 5.28 Regional Settings Menu
Regional Settings - Press the soft key to scroll through the selections. The Default is that there are no special local settings. Refer to
Appendix E, “Regional Settings”, on page 92.
SCS Settings
Use the SCS Settings softkey to access the SCS Settings screen:
Figure 5.29 SCS Settings Menu
SCS Mode - Press the soft key to select mode A or B for FSCS applications. Refer to the SCS Installation manual for additional infor-
mation. Default: A
MSCS Control Zone - Press the soft key to enter the logic equation associated with multiple smoke control stations. Refer to the SCS
manual for an MSCS programming example. The Default is that there is not an MSCS configuration.
5.5.4 Panel Timers
Use the soft key (or the arrow keys) to select a setting to change:
AUTO SILENCE changes the auto silence timer. The range is from 3, 10, 15, or 20 minutes (OFF=disabled). Default: 0FF
REGIONAL SETTINGS
REGIONAL SETTINGS: DEFAULT
ACCEPT
BACK
Main menu
Program/alter status menu
Panel Program menu
Panel settings
More
Regional Settings
SCS SETTINGS
SCS MODE: A
MSCS CONTROL ZONE: ZLXXX
ACCEPT
BACK
Main menu
Program/alter status menu
Panel Program menu
Panel settings
More
SCS Settings
NOTE: For network applications:
If Auto Silence is enabled on the NCA-2, do not enable it on the fire panel(s).
If there are multiple NCA-2s monitoring the same panels on the network, only enable Auto Silence on one NCA-2.