NFW-50X Manual — P/N LS10129-001NF-E:C 7/25/2018 59
Master Programming Level Programming
Monitor module type selection will affect the function of the point as follows:
Monitor Type Action When Activated
Pull-Station Fire Alarm
User-Defined-1 same as previous (Pull-Station)
Waterflow Fire Alarm Delayed
User-Defined-2 same as previous (Waterflow)
Monitor Fire Alarm
User-Defined-3 same as previous (Monitor)
Future not used
Future not used
Smoke-Conventional Fire Alarm
User-Defined-5 same as previous (Smoke-Conventional)
Heat Conventional Fire Alarm
User-Defined-6 same as previous (Heat-Detector)
Medic Alert
1
1 Combination systems employing these non-fire monitor types require the SLC loop to be programmed
by the installer for Class B operation and isolator modules must be employed on each non-fire branch
of the SLC as shown in the SLC Wiring Manual (document number 52304 and 515253). Fire and non-
fire devices must not be used on the same SLC branch. For UL2017 compliance, The N-ANN-LED
annunciator must be used to indicate the active, dedicated zone or device
General Purpose Signaling, latching
User-Defined-7 same as previous (Medic-Alert)
Hazard Alert
1
General Purpose Signaling, latching
User-Defined-8 same as previous (Hazard-Alert)
Tornado Alert
1
General Purpose Signaling, latching
User-Defined-9 same as previous (Tornado-Alert)
Phone Active Phone (LCD display only)
User-Defined-10 same as previous (Phone)
Tamper Supervisory, nonlatching (tracking)
User-Defined-11 same as previous (Tamper)
Supervisory Supervisory, latching
User-Defined-12 same as previous (Supervisory)
Supervisory AR
2
2 For entries ending in AR, AR refers to AutoResettable.
Supervisory, nonlatching (tracking)
User-Defined-13 same as previous (Supervisory-AR)
HVAC OVRRIDE
3
3 For HVAC RESTART and HVAC OVRRIDE descriptions, refer to “Monitor Module Operation” on
page 141.
Switch Supervisory, nonlatching (tracking)
Power Monitor Power Fault
User-Defined-14 same as previous (Power Monitor)
Trouble Monitor Trouble
User-Defined-15 same as previous (Trouble Monitor)
Process Monitor General Purpose Signaling, latching
User-Defined 16
1
same as previous (Process-Monitor)
Process Monitor AR
1,2
General Purpose Signaling, nonlatching (tracking)
User-Defined-17 same as previous (Process-Monitor-AR)
Future not used
Future not used
Ack Switch Acts like panel Acknowledge Key
Sil Switch Acts like panel Silence Key
Reset Switch Acts like panel Reset Key
Drill Switch Acts like panel Drill Key
PAS Bypass PAS Disable
HVAC RESTART
3
Switch (see note 2)
Drill Switch AR
2
Acts like panel Drill Key, non-latching (tracking)
Wireless Gateway SWIFT gateway needs this type to display wireless troubles at the FACP
Table 3.1 Monitor Types