90 NFW-50X Manual — P/N LS10129-001NF-E:C 7/25/2018
Programming Master Programming Level
ANN-LED Options
Pressing 2 for Module Options while viewing the ANN XXX Address Screen when the ANN-LED option
is selected, will display the following screens:
The first screen indicates that the N-ANN-LED at the selected ANN-BUS address is programmed to annunciate Alarms, Troubles and
Supervisories for Zones 000 through 009. The programming can be changed using ANN-LED Address Screen 2.
Pressing 1 while viewing ANN-LED Address Screen #2 will program the annunciator module to annunciate either Point (addressable
device address) information or Zone information. Each press of the 1 key will toggle the display between Point and Zone.
Pressing 2 while viewing ANN-LED Address Screen #2 will program the annunciator module to annunciate only Alarms or Alarms,
Troubles and Supervisories (ATS). Each press of the 2 key will toggle the display between Alarms and ATS.
Pressing 1 while viewing ANN-LED Address Screen #3 will select the Point or Zone range to be annunciated (refer to the tables in “N-
ANN-RLED Zone Option - Alarm Only” on page 90 and “N-ANN-RLED Point Option - Alarm Only” on page 91). Pressing the 1 key
will display an additional screen where the range can be selected.
If Zone has been selected, and Alarms Only are to be annunciated, he new screen will give the options of annunciating Zone 000 -
029 or 030 - 049. Two N-ANN-LED modules are required to annunciate all zones in this configuration.
If Zone has been selected, and Alarms, Troubles and Supervisories are to be annunciated, the new screen will give the options of
annunciating Zone 000 - 009, 010 - 019, 020 - 029, 030 - 039, or 040 - 049. Five N-ANN-LED modules are required to annunciate
all zones in this configuration.
If Points has been selected, and Alarms Only are to be annunciated, the new screen will give the options of annunciating Points 001
- 030 and 031 - 050. Two N-ANN-LED modules are required to annunciate all points in this configuration.
If Point has been selected, and Alarms, Troubles and Supervisories are to be annunciated, the new screens will give the options of
annunciating Points 001 - 010, 011 - 020, 021 - 030, 031 - 040 or 041 - 050. Five N-ANN-LED modules are required to annunciate
all points in this configuration.
N-ANN-RLED Zone Option - Alarm Only
If Zone is selected as the module option, and the module is programmed to annunciate alarms only, the first ten LEDs on the N-ANN-
RLED module will display the system status information. The remaining 30 LEDs on the first module and the last 30 LEDs on the sec-
ond module will display the active/alarm status of each zone in the Zone Range programmed for that particular module. The LED assign-
ments for each N-ANN-LED module will be as follows.
Alarm Silenced NAC 1 Fault NAC 2 Fault Not Used Not Used
Earth Fault Battery Fault Charger Fault Disabled Maintenance
Zone 000
Active/Alarm
Zone 001
Active/Alarm
Zone 002
Active/Alarm
Zone 003
Active/Alarm
Zone 004
Active/Alarm
Zone 005
Active/Alarm
Zone 006
Active/Alarm
Zone 007
Active/Alarm
Zone 008
Active/Alarm
Zone 009
Active/Alarm
Zone 010
Active/Alarm
Zone 011
Active/Alarm
Zone 012
Active/Alarm
Zone 013
Active/Alarm
Zone 014
Active/Alarm
Zone 015
Active/Alarm
Zone 016
Active/Alarm
Zone 017
Active/Alarm
Zone 018
Active Alarm
Zone 019
Active/Alarm
Zone 020
Active/Alarm
Zone 021
Active/Alarm
Zone 022
Active/Alarm
Zone 023
Active/Alarm
Zone 024
Active/Alarm
Zone 025
Active/Alarm
Zone 026
Active/Alarm
Zone 027
Active/Alarm
Zone 028
Active/Alarm
Zone 029
Active/Alarm
Table 3.4 N-ANN-RLED Module #1
Not Used Not Used Not Used Not Used Not Used
Not Used Not Used Not Used Not Used Not Used
Zone 030
Active/Alarm
Zone 031
Active/Alarm
Zone 032
Active/Alarm
Zone 033
Active/Alarm
Zone 034
Active/Alarm
Zone 035
Active/Alarm
Zone 036
Active/Alarm
Zone 037
Active/Alarm
Zone 038
Active/Alarm
Zone 039
Active/Alarm
Zone 040
Active/Alarm
Zone 041
Active/Alarm
Zone 042
Active/Alarm
Zone 043
Active/Alarm
Zone 044
Active/Alarm
Zone 045
Active/Alarm
Zone 046
Active/Alarm
Zone 047
Active/Alarm
Zone 048
Active Alarm
Zone 049
Active/Alarm
Not Used Not Used Not Used Not Used Not Used
Not Used Not Used Not Used Not Used Not Used
Table 3.5 N-ANN-RLED Module #2
ANN XXX
1=ENABLED YES
2=MODULES INSTALLED
3=AUTO-CONFIGURE
ANN-BUS XXX Screen #2
ANN-LED - ADDR X-1
ZONES 000-009
ALARM, TRBL, SUPV
ANN-LED Address Screen #1
ANN-LED - ADDR X-1
1=POINT/ZONE ZONE
2=ALARM/ATS ATS
ANN-LED Address Screen #2
ANN-LED - ADDR X-1
1=RANGE ZN000-009
ANN-LED Address Screen #3