CHAPTER
1
PW-7000 Output Module (PW7K1OUT) Installation Guide, Document 800-25675V1 1
PW-7000 OUTPUT MODULE
Description
The Output Board provides connections for 16 relay outputs. You can either mount
the board in a rack or open flat. If you rack-mount the board, only one edge is
accessible for wiring; however, a flat mount increases the amount of available I/O
slightly but significantly decreases the number of boards that can be mounted in
one enclosure.
Starting at the bottom of the rack-mount side of the board:
The first connector provides power to the board.
The next connector provides communication with the Controller (PW7K1IC or
PW6K1IC).
Continuing up this edge, the next six connectors provide 12 relay output
connections.
When the board is mounted flat, four additional relay outputs and two dedicated
inputs for cabinet tamper and power fault detection are provided on the opposite
edge of the board.
All 16 form-C relay outputs are designed to handle dry-circuit signals. The two
dedicated inputs are non-supervised. Communication to the control panel is
accomplished via an RS-485 interface. This board requires 12 VDC input power.
When communication to the controller is lost, this board maintains all previous
output settings at the time communication was lost.