EasyManua.ls Logo

Honeywell PW7K1OUT

Honeywell PW7K1OUT
22 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 PW-7000 Output Module (PW7K1OUT) Installation Guide, Document 800-25675V1
Specification
The Output Board is for use in low voltage, class 2 circuits only.
Primary power:
12VDC + 10%, 385mA maximum
Relay contacts:
Relays 0 through 15 outputs, Form-C, 2A @ 30VDC, resistive
Inputs:
Two unsupervised dedicated inputs
Communication:
Wire requirements:
Mechanical:
Environment:
RS-485
Range 9,600 to 38,400 bps
Power
1 twisted pair, 18AWG
RS-485
24AWG, 4,000 feet (1,200 m) max., 2 twisted pair with shield
(120?, 23pF) (Belden 9842 or equiv.)
Inputs
1 twisted pair per input, 30 ohms max.
Outputs
As required for the load
Dimension
5.5" (140 mm) W x 9" (229 mm) L x 1" (25 mm) H
Weight
12 oz. (340 g) nominal
Temperature
0°C to +49°C, operating, -55°C to +85°C, storage
Humidity
0% to 85% RHNC