S9200U1000 UNIVERSAL HOT SURFACE IGNITION INTEGRATED FURNACE CONTROL
15 69-2075—01
Electronic Air Cleaner
The line voltage EAC output energizes anytime the 
circulator is energized.
II. CHECK SAFETY SHUTOFF 
OPERATION
1. Shut off the gas supply at the manual gas valve 
ahead of the appliance.
2. Set the thermostat to call for heat. System should 
operate as indicated in Fig. 9 on page 17.
3. Following lockout, open the manual gas valve and 
make sure no gas is flowing to the burner.
Error Conditions
The following section lists the S9200U1000 operating 
sequence for the stated error conditions.
Main Valve Sensing
The S9200U1000 monitors the valve output during the 
following conditions:
— Idle Mode
— Non-fault related states of Ignition sequence
— States related to the pressure switch fault
— When limit switch is open and inducer is no longer 
running, up to 180 seconds following the limit 
switch opening 
In other conditions/states, main valve feedback is not 
monitored.
MAIN VALVE FEEDBACK PROCESSING
If the inducer is off or on while the pressure switch is still 
open, and voltage is detected on the valve for longer than 
the fault debouncing time (miswire):
— All outputs are turned off except for the inducer, 
which is kept energized.
— The circulator energizes at the heat speed.
— If a call for cool occurs, the control energizes the 
circulator at cool speed after the appropriate 
delay.
— An error code flashes indicating there is a hard-
ware malfunction. See Table 11 on page 20.
— An EnviraCOM™ alarm is active and sent on the 
bus. See Table 13 on page 22. 
If voltage is no longer detected on the valve for more than 
the fault debouncing time:
— If the number of detected gas valve welded/mis-
wire conditions have not reached 5 (since last 
power-up), the S9200U1000 proceeds to Soft 
Lockout. The S9200U1000 remains in Soft Lock-
out for the Auto Restart Delay. 
— If the number of detected gas valve welded/mis-
wire conditions have reached 5 (since last power-
up), the S9200U1000 enters Hard Lockout, where 
it remains until power reset. 
An EnviraCOM™ alarm indicating that manual 
reset is needed is active and sent on the bus. See 
Table 13 on page 22.
If the inducer is energized or the pressure switch is closed 
and the inducer is not energized (pressure switch is stuck 
closed) and the main valve relay contacts are sensed 
closed even though the relay is not energized (welded 
contacts):
— An error code flashes indicating there is a hard-
ware malfunction. See Table 11 on page 20. 
— An EnviraCOM™ alarm is active and sent on the 
bus. See Table 13 on page 22.
— The inducer immediately switches off in an 
attempt to open the pressure switch. If, after 5 
seconds, flame is sensed or voltage is still sensed 
on the main valve, the S9200U1000 energizes the 
inducer and circulator on heat speed.
If flame is not sensed and voltage on the main valve is no 
longer detected:
— The S9200U1000 proceeds to Soft Lockout if the 
number of detected gas valve welded/ miss-wire 
conditions have not reached 5 (since last power-
up). The S9200U1000 remains in Soft Lockout for 
the Auto Restart Delay period. Otherwise, the 
S9200U1000 will enter Hard Lockout where it will 
remain until power is reset.
If voltage is not detected on the valve for longer than the 
fault debouncing time during a period when the valve is to 
be energized (contacts failed to make):
— the S9200U1000 proceeds as if flame is not 
sensed. If Soft Lockout is entered due to this con-
dition:
• An error code flashes indicating failed 
hardware. See Table 11 on page 20. 
• An EnviraCOM™ alarm is active and sent on 
the bus. See Table 13 on page 22.
Flame Out of Sequence
The S9200U1000 does not take action on flame sensed in 
Idle Mode when there is no call for heat present.
If the S9200U1000 is servicing a call for heat and flame is 
sensed when it is not expected to be present, the ignition 
and fan sequences are not allowed to progress and the 
S9200U1000 stays in its current state. The exception is 
Igniter Warmup, where the S9200U1000 proceeds to 
Prepurge.
If the sensed flame goes away before the False Flame 
Recognition Period, the ignition sequence proceeds as 
normal. 
If however the sensed flame lasts longer than the False 
Flame Recognition Period: 
— The igniter de-energizes, the inducer energizes, 
and the circulator energizes at heat speed. 
— An error code flashes indicating flame is sensed 
out of sequence. See Table 11 on page 20.
— An EnviraCOM™ alarm is active and sent on the 
bus. See Table 13 on page 22.
— When the sensed flame goes away, the 
S9200U1000 proceeds to Postpurge, followed by 
Idle Mode at which time the error code is cleared.