S9360A, S9361A, S9380A, S9381A INTEGRATED BOILER CONTROLLERS
7 66-1203—05
Table 4. Specific Ignition Timings.
a
Ignition Activation Period is the time that the hot surface igniter remains powered after the gas valve opens.
b
Purge Timing specified in seconds.
c
Models available in both—separate and combined igniter/sensor type.
d
90 second Trial for Ignition. Continuous Recycles/Retries.
e
S3961A2095 has a 1 minute retry delay and a 5 minute recycle delay. Other lockouts will automatically clear after
1 hour.
Model
Ignition
Type Draft Type
No. of
Ignition
Trials
Igniter/
Sensor
Type
Automatic
Restart
Time
e
Ignition
Activation
Period
a
Prepurge
Timing
b
Postpurge
Timing
b
S9360A,
S9361A
Intermittent
Pilot - Spark
Induced 6 Separate/
Combined
c
1 hour N/A 30 15
S9360A,
S9361A
Intermittent
Pilot - Spark
Atmospheric 6 Separate/
Combined
c
1 hour N/A 1 5
S9361A2095
d
Intermittent
Pilot - Spark
Atmospheric Continuous Combined 1 hour N/A 0 0
S9381A Direct Spark Induced 3 Combined 1 hour N/A 15 15

Other manuals for Honeywell S9360A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell S9360A and is the answer not in the manual?

Honeywell S9360A Specifications

General IconGeneral
BrandHoneywell
ModelS9360A
CategoryController
LanguageEnglish

Related product manuals