Calibration Handbook
126
Sensepoint XCD
20. When the reading falls below 50% of the calibration gas level the display indicates a countdown (up to
180 seconds dependant on gas type).
21. When the countdown is finished, the calibration procedure is complete.
22. The instrument returns to the ‘Set CAL menu. Activate the ‘ or ‘! switch to select another menu or
select ‘QuIT’ to return to normal monitoring mode.
NOTE
K$A$A>$)&+(&/<I/"'&)$1</2$&+?$&L$/+?$)&M)(+$2+.(%&/%*&(+?$)&/22$''().$'3
Zero and Span Calibration of Hydrogen Sulfide sensors
Hydrogen Sulfide sensors can be affected by extreme hu
midity changes. A sudden increase in ambient humidity
can result in a short-term positive drift in the instrument’s reading. A sudden decrease in ambient humidity
can result in a short-term negative drift in the instrument’s reading. These are most likely to be noticed during
calibration with dry or cylinder gas.
When calibrating Hydrogen Sulfide cartridges the following should be taken into account while following the
Span/Zero procedure:
1. To zero the sensor, use a compressed air cylinder of 20.9%Vol oxygen (not Nitrogen). Do not use
background air.
2. Apply the gas to the sensor for three minutes before using to confirm the zero calibration.
3. If a span calibration is to be performed, the span calibration gas should be applied to the sensor immediately
after the zeroing procedure. Do not allow the sensor to return to ambient air conditions between steps
2 and 3.
4. Apply the span gas for two minutes before using to confirm the span calibration.

Other manuals for Honeywell Sensepoint XCD

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Sensepoint XCD and is the answer not in the manual?

Honeywell Sensepoint XCD Specifications

General IconGeneral
TypeFixed Gas Detector
Ingress ProtectionIP66/67
DisplayLCD
Output4-20 mA, Relay
CertificationATEX, IECEx
Sensor TypeElectrochemical, Infrared
Humidity0 to 99% RH (non-condensing)
MaterialStainless Steel
Detection PrincipleDepends on Sensor Type
Power Supply24 VDC nominal (17-32 VDC)

Related product manuals