SWIFT® Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000SK-E:G 4/13/2020 21
Operations WSK-WGI Wireless System Gateway
3. From the Home Screen, select the Site Survey, Create Mesh Network, or Diagnostics function.
4. Click Operations. The following screen is displayed.
5. Select Gateway Operations to lock/unlock the gateway. The Lock/Unlock Gateway screen displays the list of gateway/gateways
that are in the range of the W-USB adapter connected to your /Laptop.
6. Select desired gateway and click Lock or Unlock as required.
To lock the gateway
1. Click Lock. The Gateway Password screen is displayed.
2. Enter the verification password in the Verification Password field and click OK.
3. A Hall Sensor Activation window displays. The LED on the gateway blinks yellow indicating the gateway is waiting for
hall sensor activation.
4. Place a magnet on either of the gateway sensors within 120 seconds.
5. The LED blinks normal upon hall sensor activation. The gateway is locked and a confirmatory message is displayed.
To unlock the gateway
1. Click Unlock. The Gateway Password screen is displayed.
2. Enter the verification password in the Verification Password field and click OK.
Figure 2.18 Operations Menu
operations.jpg
lock_unlcok_gateway.jpg
Figure 2.19 Lock/Unlock Screen
hall sensor.png