SWIFT® Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000SK-E:G 4/13/2020 39
Wiring W-SYNC Wireless Synchronization Module
4.2.2 HPFF8/HPFF12 NAC Expander
When using the HPFF8 or HPFF12 to power the W-SNYC module, set the DIP switches on the HPFF8/HPFF12 as follows:
•SW1- OFF
•SW2- OFF
•SW3- OFF
•SW4- OFF
•SW5- ON
•SW6- OFF
Wire the W-SYNC to the HPFF8/12 as follows):
TB3
TB4
TB1
TB2
REF+ REF– + IN – IN
+ OUT
– IN
+ OUT
+ IN
– OUT
– OUT
SIGNAL 1
SIGNAL 2
BATT+ BATT–
A+
N/O
N/C
COMM
N/O
N/C
COMM
AC FAIL
TROUBLE
1L1 1L2 2L1 2L2
3L1 3L2
4L1 4L2A–
+
-
+ -
HPFF8/HPFF12
W-SYNC
3.9KΩ ELR
Figure 4.2 W-SYNC Wiring to HPFF8/HPFF12
C NC
24VDC Power
power supply
trouble input
synchronized
output