355
Balance
Point
(Compressor
Lockout)
Off, 5 °F to 60 °F (in 5 °F
increments) or
-15.0 °C to 15.5 °C (in 2.5 °C
or 3.0 °C increments)
Compressor Lockout requires an outdoor
temperature. Set Compressor Lockout to the
temperature below which it is inefficient to run the
heat pump. When outside temperature is below
this setting, thermostat will lockout heat pump and
run Aux Heat only. This ISU is only displayed if
ISU 130 = Wired or Internet, ISU 200 is set to
Heat Pump, ISU 221 Aux/E stages = 1, AND ISU
260 is set to Thermostat. We recommend using a
wired remote sensor as an outdoor temperature
source.
Default is 40 °F (4.4 °C) if ISU 205 Heating
Equipment is Air to Air Heat Pump and ISU 255
Aux Heat Type is Gas/Oil.
Default is Off if ISU 205 Heating Equipment is Air
to Air Heat Pump and ISU 255 Aux Heat Type is
Electric. Default is Off if ISU 205 Heating
Equipment is Geothermal.
Compressor Lockout is optional for any type of
heat pump (Air to Air Heat Pump, Geothermal
Heat Pump).
356
Aux Heat
Lock Out
(Aux Heat
Outdoor
Lockout)
Off, 5 °F to 65 °F (in 5 °F
increments) or
-15.0 °C to 18.5 °C (in 2.5 °C
or 3.0 °C increments)
Aux Heat Lockout requires an outdoor
temperature. Set Aux Heat Lockout to optimize
energy bills and to not allow it to run the more
expensive Aux Heat source above certain outdoor
temperature limit. This ISU is only displayed if ISU
200 is set to Heat Pump, AND ISU 260 is set to
Thermostat control AND if ISU 221 Aux/E stages
= 1.
365
Cool 1 CPH
(Cooling
cycle rate
stage 1)
1 – 6 CPH (3 CPH)
This ISU is only displayed when Cool
/Compressor Stages is set to 1 or more stages.
Cycle rate limits the maxi- mum number of times
the system can cycle in a 1 hour period measured
at a 50% load. For example, when set to 3 CPH,
at a 50% load, the most the system will cycle is 3
times per hour (10 minutes on, 10 minutes off).
The system cycles less often when load conditions
are less than or greater than a 50% load.
366
Cool 2 CPH
(Cooling
cycle rate
stage 2)
1 – 6 CPH (3 CPH)
This ISU is only displayed when Cool
/Compressor Stages is set to 2.

Other manuals for Honeywell T6 Pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell T6 Pro and is the answer not in the manual?

Honeywell T6 Pro Specifications

General IconGeneral
DisplayTouchscreen
Energy Star CertifiedYes
Power SourceBattery or Hardwired
Operating ModesHeat, Cool, Auto, Off
GeofencingYes
CompatibilityWorks with most HVAC systems
Fan ModesAuto, On, Circulate
Remote AccessYes
Energy Saving FeaturesSmart Response Technology
ConnectivityWi-Fi
Warranty5-year limited warranty

Related product manuals