Table 8. Installer System Test Options.
NOTE: Press any key and the numbers will change on the
display. Press Time ▼ ▼ to go to the previous test and
Time ▲▲ to go to the next test. The Run Program Key
will not exit from this test. To exit, go to a different
test and press Run Program.
THERMOSTAT INFORMATION
1. Press the Time ▲ ▲ Key to access the thermostat
information.
2. Press the increase ▲ key to display the production date
code. The first two large digits are the month and the
third digit is the last digit of the year (Example: 027=
February 1997).
M4934
M10351
3. Press the increase ▲ key again to display the software
identification code. (Example: 02 = software ID code 2)
M4932A
Key to
Press
Test
Number Description
Heating Equipment System Test
Time ▲ 10 Enter heating equipment System Test.
▲ 11 Stage-one heat comes on. The system fan is also energized.
▲ 12 Stage-two heat comes on. Stage-one heat and system fan remain on.
▼ 11 Stage-two heat turns off.
▼ 10 Stage-one heat and system fan turn off.
Emergency Heating Equipment System Test
Time ▲ 20 Change from heating to emergency heating equipment System Test.
▲ 21 Emergency heat comes on.
▼ 20 Emergency heat turns off.
Cooling Equipment System Test
Time ▲ 30 Change from heating or emergency heating to cooling equipment System Test.
▲ 31 Cool and system fan come on.
▼ 30 Cool and system fan turn off.
Fan Equipment System Test
Time ▲ 40 Change from cooling to fan equipment System Test.
▲ 41 Fan comes on.
▼ 40 Fan turns off.
Key Operation System Test
Time ▲ 60 2 Change from fan to key operation System Test.