EasyManua.ls Logo

Honeywell TB6575B1000/U - SuitePro Digital Fan Coil Stat - Page 5

Honeywell TB6575B1000/U - SuitePro Digital Fan Coil Stat
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TB6575/TB8575 DIGITAL FAN COIL THERMOSTATS
5 62-0311—05
N: Line voltage ground (120/240 Vac)
Ps: Pipe sensor (optional)
R: 24 Vac power
Rs: Remote sensor (optional)
SB: Remote setback (optional)
Sc: Ground (required if remote sensor, pipe sensor,
and/or remote setback are connected)
W/Y: W = Heating; Y = Cooling (2 pipe only)
Y/A: Y = Cooling; A = Electrical heater output
Table 3. Terminal Wiring.
Model Application
Terminals
12 34567891011
TB6575A1000 — 120/240 Vac
Terminal Identifier
LW/Y Y/AGlGmGhNRs
a
a
Rs; Remote sensor is optional.
Sc
b
b
Required when Rs, SB, or Ps is wired.
SB
c
c
SB; Remote setback is optional.
Ps
d
d
Pipe sensor: Discrete, Analog, or Aquastat®.
Fly lead wire color
Black Orange Yellow Red Blue Brown White None
e
e
These terminals (8, 9, 10, and 11) do not have lead wires attached to them.
2 pipes; Heat only
9
f
f
A check mark (9) indicates the terminal is used in that application. Rs and SB terminal connections are optional. If a
terminal is left blank, it is not used in that application.
W
99 9 9
O
g
g
O = Optional
R
h
h
R = Required if Rs, SB, or Ps is wired.
O
2 pipes; Cool only
9
Y
99 9 9
ORO
2 pipes; Heat or Cool with Manual Changeover
9
W/Y
99 9 9
ORO
2 pipes; Heat or Cool with Seasonal Changeover
9
W/Y
99 9 9
ORO9
4 pipes; Heat and Cool with Manual Changeover
9
WY
99 9 9
ORO
4 pipes; Heat and Cool with Auto Changeover
9
WY
99 9 9
ORO
2 pipes; Heat or Cool with Auxiliary Heat
9
W/Y A
99 9 9
ORO9
4 pipes; Heat and Cool with Manual Changeover or Auto Changeover
9
WY
99 9 9
ORO
TB6575B1000 — 120/240 Vac
Terminal Identifier
LW/Y n/a
i
i
Terminal 3 is not used on the TB6575B1000 model.
Gl Gm Gh N Rs
a
Sc
b
SB
c
Ps
d
Fly lead wire color
Black Orange Red Blue Brown White None
e
2 pipes; Heat only
9
W
99 9 9
ORO
2 pipes; Cool only
9
Y
99 9 9
ORO
2 pipes; Heat or Cool with Manual Changeover
9
W/Y
99 9 9
ORO
2 pipes; Heat or Cool with Seasonal Changeover
9
W/Y
99 9 9
ORO9
TB8575A1000 — 24 Vac
Terminal Identifier
j
j
The TB8575A1000 model does not have fly lead wires attached to any terminals.
RW/YY/AGlGmGhCRs
a
Sc
b
SB
c
Ps
d
2 pipes; Heat only
9
W
99 9 9
ORO
2 pipes; Cool only
9
Y
99 9 9
ORO
2 pipes; Heat or Cool with Manual Changeover
9
W/Y
99 9 9
ORO
2 pipes; Heat or Cool with Seasonal Changeover
9
W/Y
99 9 9
ORO9
4 pipes; Heat and Cool with Manual Changeover
9
WY
99 9 9
ORO
4 pipes; Heat and Cool with Auto Changeover
9
WY
99 9 9
ORO
2 pipes; Heat or Cool with Auxiliary Heat
9
W/Y A
99 9 9
ORO9
4 pipes; Heat and Cool with Manual Changeover or Auto Changeover
9
WY
99 9 9
ORO

Related product manuals