TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS
62-2018—05 6
If LED indicator is desired at the TB-WALL-OVR-1014:
1. Set the Aux Cont installer parameter (which controls BO5) to option 2, Auxiliary NC.
2. Install a jumper across the BO5 terminal and 24 Vac Hot.
Fig. 5. Wiring example of single remote wall mounted room sensor
Fig. 6. Wiring examples of two remote wall mounted room sensors for averaging applications
Fig. 7. Wiring examples of three remote wall mounted room sensors for averaging applications
Scom
RS
BO 5
24 VAC
COM
BI 2
Scom
RS
AUX
C
DI
Scom
RS
TB7200/TB7300
THERMOSTAT
TB7200/TB7300
THERMOSTAT
TB-WALLOVR-1014 TB-WALL-1014
DIP SWITCHES
S1 = ON S2 = ON
DIP SWITCHES
S1 = ON S2 = ON
REMOTE WIRING 1 SENSOR
M32847
Scom
RS
BO 5
24 VAC
COM
BI 2
Scom
RS
AUX
C
DI
Scom
RS
TB-WALLOVR-1014 TB-WALL-1014
DIP SWITCHES
S1 = ON
S2 = OFF
DIP SWITCHES
S1 = ON
S2 = OFF
REMOTE WIRING 2 SENSORS
M32848A
Scom
RS
TB-WALL-1014
Scom
RS
TB-WALL-1014
TB-WALL-1014 AND TB-WALLOVR-1014 CAN BE MIXED AND MATCHED
TB-WALL-1014 AND TB-WALLOVR-1014 ARE TO BE WIRED IN PARALLELL
ENSURE THE DIP SWITCH SETTINGS ARE CORRECT IN EACH REMOTE SENSOR
1
1
Scom
RS
AUX
C
DI
TB-WALLOVR-1014
DIP SWITCHES
S1 = ON
S2 = OFF
Scom
RS
AUX
C
DI
TB-WALLOVR-1014
TB7200/TB7300
THERMOSTAT
TB7200/TB7300
THERMOSTAT
TB7200/TB7300
THERMOSTAT
DIP SWITCHES
S1 = ON
S2 = OFF
DIP SWITCHES
S1 = ON
S2 = OFF
DIP SWITCHES
S1 = ON
S2 = OFF
Scom
RS
BO 5
24 VAC
COM
BI 2
Scom
RS
BO 5
24 VAC
COM
BI 2
Scom
RS
BO 5
24 VAC
COM
BI 2
Scom
RS
AUX
C
DI
TB-WALLOVR-1014
DIP SWITCHES
S1 = OFF
S2 = OFF
ALL DIP SWITCHES
S1 = OFF
S2 = OFF
REMOTE WIRING 3 SENSORS
M32849A
Scom
RS
TB-WALL-1014
Scom
RS
TB-WALL-1014TB-WALL-1014TB-WALL-1014
Scom
RS
TB-WALL-1014
TB7200/TB7300
THERMOSTAT
TB7200/TB7300
THERMOSTAT
Scom
RS
Scom
RS
Scom
RS
BO 5
24 VAC
COM
BI 2
Scom
RS
BO 5
24 VAC
COM
BI 2
DIP SWITCHES
S1 = OFF
S2 = OFF
TB-WALL-1014 AND TB-WALLOVR-1014 CAN BE MIXED AND MATCHED
TB-WALL-1014 AND TB-WALLOVR-1014 ARE TO BE WIRED IN PARALLELL
ENSURE THE DIP SWITCH SETTINGS ARE CORRECT IN EACH REMOTE SENSOR
1