VISIONPRO® 8000 SMART THERMOSTAT
33-00096—04 20
315 Heat Cycles Per
Hour Stage 2
Note: Depending on
the application, the
text displayed on
the screen may
show the specific
heating equipment
type.
1 to 12 CPH
Conv. Forced Air = 5
CPH
Heat Pump =
3 CPH
Radiant Heat = 3 CPH
Both This ISU is only displayed when ISU 207 Heat Stages
is set to 2 stages.
Cycle rate limits the maximum number of times the
system can cycle in a 1 hour period measured at a
50% load. For example, when set to 3 CPH, at a
50% load, the most the system will cycle is 3 times
per hour (10 minutes on, 10 minutes off). The
system cycles less often when load conditions are
less than or greater than a 50% load. The
recommended cycle rate settings are below for each
heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH
High Efficiency Gas Forced Air = 3 CPH
Oil Forced Air = 5 CPH
Electric Forced Air = 9 CPH
Hot Water Fan Coil = 3 CPH
Hot Water Radiant Heat = 3 CPH
Geothermal Radiant Heat = 3 CPH
Steam = 1 CPH
Gravity = 1 CPH
315 Heat Cycles Per
Hour Stage 3
Note: Depending on
the application, the
text displayed on
the screen may
show the specific
heating equipment
type.
1 to 12 CPH
Conv. Forced Air = 5
CPH
Heat Pump =
3 CPH
Radiant Heat = 3 CPH
Both This ISU is only displayed when ISU 207 Heat Stages
is set to 3 stages.
Cycle rate limits the maximum number of times the
system can cycle in a 1 hour period measured at a
50% load. For example, when set to 3 CPH, at a
50% load, the most the system will cycle is 3 times
per hour (10 minutes on, 10 minutes off). The
system cycles less often when load conditions are
less than or greater than a 50% load. The
recommended cycle rate settings are below for each
heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH
High Efficiency Gas Forced Air = 3 CPH
Oil Forced Air = 5 CPH
Electric Forced Air = 9 CPH
Hot Water Fan Coil = 3 CPH
Hot Water Radiant Heat = 3 CPH
Geothermal Radiant Heat = 3 CPH
Steam = 1 CPH
Gravity = 1 CPH
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both Notes