VISIONPRO® 8000 SMART THERMOSTAT
33-00096—04 34
1014 Vent During Hum or
Dehum Calls
Yes
No
Yes Both This feature is used to help reach the user's desired
humidity level by not allowing the ventilation
equipment to run during a call for humidification or
dehumidification.
Yes: Ventilation is allowed to run during a call for
humidification or dehumidification.
No: Ventilation is NOT allowed to run during a call for
humidification or dehumidification.
1016 Vent On High
Indoor Humidity
Off
On
On Both This ISU is only displayed when ISU 1000
Ventilation Type is set to ERV / HRV.
Off: The humidity level has no effect on ventilation.
On: The thermostat removes excess humidity by
turning on the ventilator when the indoor humidity
rises 10% above the user's humidification setting.
The thermostat must be in the heat mode to
ventilate on high humidity.
1017 Ventilator Core
Reminder
Off
3, 6, 9, 12 Calendar Months
Off Both Ventilator Core Cleaning Reminder
1017 Ventilator Filter
Reminder
Off
3, 6, 9, 12 Calendar Months
Off Both Ventilator Filter Cleaning Reminder
1100 Number of UV
Devices
0, 1, 2
0 Both Press the up/down arrows to select the number of UV
devices installed in the system. Some systems may
have two UV devices, one for the A-Coil and another
for Air Treatment. A replacement reminder can be
setup for each one. Select 0 if no UV devices are
installed.
1105 UV Bulb 1 Reminder
Note: “1” is not
displayed if there is
only 1 UV Bulb
Off, 6, 12, 24 Calendar Months
Off Both UV Bulb 1 Replacement Reminder
1105 UV Bulb 2 Reminder
Off, 6, 12, 24 Calendar Months
Off Both UV Bulb 2 Replacement Reminder
1200 Custom Reminders
View / Edit Custom Reminders
Add Custom Reminders
None Both See “Customizable Reminders” beginning on
page 72.
28 Backlighting
On Demand
Continuous
On Demand Both Select Continuous or On Demand backlighting.
Select Continuous backlighting if you would like the
backlight to be on all the time.
Select On Demand backlighting if you would like the
backlight to only turn on after a key press. After you
complete your changes, the screen stays lit for 45
seconds.
1400 Clock Format
12 hour
24 hour
12 Both
1401 Daylight Saving
Time
Off
On
On Both Set to Off in areas that do not follow Daylight Saving
Time.
1402 Indoor Temperature
Offset
-3° F to 3° F (in 1° F increments)
0° F Both 0° F - No difference in displayed temperature and
the actual room temperature.
The thermostat displays up to 3°F (1.5°C) lower or
higher than the actual measured temperature.
1402 Show humidity on
home screen
Yes
No
Yes Both This option is only available if humidifier type and
dehum equipment are both set to none.