MASTERTROL® AUTOMATIC BALANCING SYSTEM™ (MABS®) EZ ZONE (EZ-2 AND EZ-4) CONTROL PANELS
9 69-1360–2
OPERATION
Sequence of Operation
On a call for heating or cooling, the zone damper to the calling 
zone stays open, and the dampers close to the zones that are 
not calling. The MABS EZ panel brings on the heating or 
cooling and conditioned air is delivered to the calling zone 
until the zone is satisfied. When the call is satisfied, the 
system enters the Purge mode. This holds open the damper 
of the last zone calling and purges into that zone. The Purge 
time can be set to three and one-half or two minutes. 
Individual Zone Fan Control
When all zones are satisfied, each zone thermostat Fan 
switch controls the fan operation for each zone. When 
circulation is desired, place the Fan switch in the On position. 
The fan runs and closes the dampers to the zones where the 
Fan switch is set to Auto. 
Multi-Stage Operation
MABS-EZ can control up to two stages of heating and cooling 
using singe-stage thermostats. The panel uses a timer to 
control the second stage and is adjustable from five minutes 
to 30 minutes using DIP switches 5, 6, and 7. See Table 4.
When a call for heating or cooling is not satisfied within the 
time set on the stage time, the panel energizes the second 
stage of heat or cool and both stages remain on until the call 
is satisfied.
Changeover Operation
The MABS EZ panel uses a standard heating and cooling 
thermostat for each zone to allow any zone to call for heating 
or cooling. When opposite calls are made from different 
zones, MABS EZ accepts the first call. Once the first call is 
satisfied, or a maximum of 20 minutes elapses from the start 
of an opposite call, MABS EZ allows the opposite call. 
Automatic changeover thermostats can also be used to 
provide automatic zone changeover. 
When opposite calls occur, the panel ensures that both calls 
are acknowledged. If the first call is not satisfied within 20 
minutes, the panel drops the existing call and goes into the 
Purge mode. After completion of the Purge, the panel 
switches to the opposite mode until it is satisfied or until 20 
minutes elapses.Then it goes back into the Purge mode and 
back to the original call. The system continues to switch back 
and forth until both calls are satisfied.
Purge Mode
At the end of every call for heat or cool, the panel enters a 
Purge mode that holds the last zone damper open for three 
and one-half or two minutes. During this time, the panel or 
HVAC equipment can operate the fan. Purge is a time delay 
that prevents short cycling of the heating and cooling 
equipment after each call. The Purge LED lights when the 
system is in Purge mode. Press Purge Override button when 
the purge LED is lighted to override Purge.
Table 4. Stage timer configuration.
Minutes DIP Switch 5 DIP Switch 6 DIP Switch 7
5 Off Off Off
8On Off Off
10 Off On Off
12 On On Off
15 Off Off On
20 On Off On
25 Off On On
30 On On On
Table 4. Stage timer configuration.
Minutes DIP Switch 5 DIP Switch 6 DIP Switch 7