UDC2800 Universal Digital Limit Controller Quick Start Guide
Step Operation Press Result
1 Enter Set Up Mode Setup key Enter in the first set up group, Security.
2 Select any Set Up group
Setup key or Increment
or Decrement keys
Sequentially displays the other set up groups shown in the prompt hierarchy.
See Configuration Record Sheet for prompts.
You can also use the Increment or Decrement keys to scan the set up groups
in both directions. Stop at the set up group tile that describes the group of
parameters you want to configure. Then proceed to the next step.
3
Select a Function
parameter
Function key Enter in the first function prompt of the selected set up group.
Increment or
Decrement keys
Press Increment or Decrement keys to display the other function prompts of
the selected set up group. Stop at the function prompt that you want to
change.
4
Change the Value or
Selection
Function key Enter in the value or selection of the selected function prompt.
Increment or
Decrement keys
Increment or decrement the value or selection that appears for the selected
function prompt.
You can press the Increment and Decrement keys at the same time to move the
current editable digit one step left.
5
Enter the Value or
Selection
Function key Enter value or selection made into memory.
6 Exit Configuration Lower Display key Exit the set up mode and returns to the main screen.
Configuration Procedure
Configuration Record Sheet
Enter the value or selection for each prompt on this sheet so you will have a record of how your controller was configured.
Group Prompt Function Prompt Value or
Selection
Factory
Setting
Group Prompt Function Prompt Value or
Selection
Factory
Setting
Security
Password
Lockout
FM version
Restore Settings
Restore*
Change Password
――――
――――
――――
――――
――――
――――
0
Calibration
Disable
Disable
Disable
- -
Alarms
A1S1 Type
A1S1 Value
A1S1 State
A1S1 Delay
A1S1 Hysteresis
A1S2 Type
A1S2 Value
A1S2 State
A1S2 Delay
A1S2 Hysteresis
A2S1 Type
A2S1 Value
A2S1 State
A2S1 Delay
A2S1 Hysteresis
A2S2 Type
A2S2 Value
A2S2 State
A2S2 Delay
A2S2 Hysteresis
Alarm Output 1
Alarm Blocking
AO/CO Diagnostic
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
None
90
High Alarm
0
0.1
None
10
Low Alarm
0
0.1
None
95
High Alarm
0
0.1
None
5
Low Alarm
0
0.1
Non Latching
Disable
Disable
Limit Control Low or High Limit
Power Up Status
SP High Limit
SP Low Limit
――――
――――
――――
――――
High Limit
Normal
1000
0
Input1
Input 1 Type
Input 1 Transmitter
Input 1 High Value
Input 1 Low Value
Input 1 Bias
Input 1 Filter
Input 1 Burnout
――――
――――
――――
――――
――――
――――
――――
0-10 mV
Linear
1000
0
0
1
No Burnout
Options
Auxiliary Output
DI 1 Function
――――
――――
Disable
None
Display Decimal Digits
Temperature Unit
Language
TC Diagnostics
Theme
――――
――――
――――
――――
――――
None
None
English
Enable
White/Black
51-52-25-166, Revision 1.0
November 2022
Group Prompt Function Prompt Value or Selection Factory Setting
Communication
Bluetooth Function
Bluetooth ID
Bluetooth MAC Address
Communication Type
Modbus Address
Baud Rate
Response Delay
Word Order for Float
Ethernet Address
Subnet Mask Address
Default Gateway
Shed Function
Shed Time
Shed Mode
Shed SP Recall
Computer SP Unit
Local Loopback
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
Disable
UXXXXXXXX
XX:XX:XX:XX:XX:XX
Disable
3
19200
1
FP B 0123
10.0.0.2
255.255.255.0
0.0.0.0
Disable
30
Last Mode
To Local SP
Engineering Unit
Disable
Communication with RS485
board (Accessible via
Communication set up group or
Honeywell EasySet)
Bluetooth Function
Bluetooth ID
Bluetooth MAC Address
Communication Type
Modbus Address
Baud Rate
Response Delay
Word Order for Float
Shed Function
Shed Time
Shed Mode
Shed SP Recall
Computer SP Unit
Computer SP Ratio
Computer SP Bias
Local Loopback
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
Disable
UXXXXXXXX
XX:XX:XX:XX:XX:XX
Disable
3
19200
1
FP B 0123
Disable
30
Last Mode
To Local SP
Engineering Unit
1.00
0
Disable
Communication with Ethernet
board (Accessible via
Communication set up group or
Honeywell EasySet)
Bluetooth Function
Bluetooth ID
Bluetooth MAC Address
Communication Type
Modbus Address
Baud Rate
Response Delay
Word Order for Float
Ethernet Address
Subnet Mask Address
Default Gateway
Shed Function
Shed Time
Shed Mode
Shed SP Recall
Computer SP Unit
Computer SP Ratio
Computer SP Bias
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
Disable
UXXXXXXXX
XX:XX:XX:XX:XX:XX
Disable
3
19200
1
FP B 0123
10.0.0.2
255.255.255.0
0.0.0.0
Disable
30
Last Mode
To Local SP
Engineering Unit
1.00
0
Status
Software Version Read only - -
Configuration Record Sheet