04/08  UDC3200 Universal Digital Controller Operator Manual  27 
Function
Prompt
Lower Display
Selections or
Range of Setting
Upper Display
Parameter Definition 
RSET2MIN
RSET2RPM
0.02 to 50.00  These are the same as above except that they apply to Duplex 
models for the "COOL" zone of Heat/Cool applications or for the 
second set of PID constants.
CYC SEC
or
CYC SX3
1 to 120 
CYCLE TIME (HEAT) determines the length of one time 
proportional output relay cycle. Defined as "HEAT" cycle time for 
Heat/Cool applications. 
CYC SEC—Electromechanical relays 
CYC SX3—Solid state relays 
 ATTENTION  Cycle times are in either second or 1/3-second 
increments depending upon the configuration of RLY TYPE in the 
Output Algorithm Set Up group. 
CYC2 SEC 
or
CYC2 SX3
1 to 120 
CYCLE TIME 2 (COOL) is the same as above except it applies to 
Duplex models as the cycle time in the "COOL" zone of Heat/Cool 
applications or for the second set of PID constants. 
CYC2 SEC—Electromechanical relays 
CYC2 SX3—Solid state relays 
 ATTENTION  Cycle times are in either second or 1/3-second 
increments depending upon the configuration of RLY TYPE in the 
Output Algorithm Set Up group.
SECURITY
0 to 9999
SECURITY CODE—The level of keyboard lockout may be 
changed in the Set Up mode. Knowledge of a security code may 
be required to change from one level to another. This configuration 
should be copied and kept in a secure location. 
NOTE: The Security Code is for keyboard entry only and is not 
available via communications. 
 ATTENTION  Can only be changed if LOCKOUT selection is 
NONE.
LOCKOUT LOCKOUT applies to one of the functional groups: Configuration, 
Calibration, Tuning, Accutune. DO NOT CONFIGURE UNTIL ALL 
CONFIGURATION IS COMPLETE.
NONE
NONE—No lockout; all groups are read/write.
CALIB
CALIB—All groups are available for read/write except for the 
Calibration and Keyboard Lockout groups.
+ CONF 
+ CONF—Tuning, SP Ramp, and Accutune groups are read/write. 
All other groups are read only. Calibration and Keyboard Lockout 
groups are not available.
+ VIEW 
+ VIEW—Tuning and Setpoint Ramp parameters are read/write. 
No other parameters are viewable.
MAX
MAX—Tuning and Setpoint Ramp parameters are available for 
read only. No other parameters are viewable.