04/08  UDC3200 Universal Digital Controller Operator Manual  47 
Function Prompt
Lower Display
Selections or
Range of Setting
Upper Display
Parameter
Definition
NO FS 
NO FAILSAFE—This selection does not provide 
input failure detection and should only be used when 
a thermocouple input is connected to another 
instrument which supplies the Burnout current. (For 
this selection, no burnout signal is sent to the 
sensor.)
 ATTENTION   For Burnout to function properly on a 
0-20 mA input type (or a 0-5V type that uses a 
dropping resistor), the dropping resistor must be 
remotely located (across the transmitter terminals).  
Otherwise, the input at the instrument terminals will 
always be 0 mA (i.e., within the normal operating 
range) when the 0-20 mA line is opened.
EMISSIV2
0.01 to 1.00 
EMISSIVITY is a correction factor applied to the 
Radiamatic input signal that is the ratio of the actual 
energy emitted from the target to the energy which 
would be emitted if the target were a perfect radiator.
Available only for Radiamatic inputs.