54  UDC3200 Universal Digital Controller Operator Manual  04/08 
Function
Prompt
Lower Display
Selections or
Range of Setting
Upper Display
Parameter
Definition
LOW VAL 
Low Scale Value 
within the range of 
the selected 
variable to 
represent the 
minimun output (0 
or 4 mA) 
AUXILIARY OUTPUT LOW SCALING FACTOR— This is a value 
in engineering units used to represent all AUX OUT parameters 
except Output. 
For Output, this is a value in percent and can be any value 
between –5 % and +105 %.  However, keep in mind that relay 
output types can only be scaled 0 % to 100 %.
HIGH VAL 
High Scale Value 
within the range of 
the selected 
variable to 
represent the 
maximum output 
(20 mA) 
AUXILIARY OUTPUT HIGH SCALING FACTOR— This is a value 
in engineering units used to represent all AUX OUT parameters 
except Output. 
For Output, this is a value in percent and can be any value 
between –5 % and +105 %.  However, keep in mind that relay 
output types can only be scaled 0 % to 100 %. 
DIG INP1  DIGITAL INPUT 1 SELECTIONS—All selections are available for 
Input 1. The controller returns to its original state when contact 
opens, except when overruled by the keyboard. 
NONE
NO DIGITAL INPUT SELECTIONS
TO MAN 
TO MANUAL—Contact closure puts the affected loop into manual 
mode. Contact open returns controller to former mode. 
TO LSP 
TO LOCAL SETPOINT—When a remote setpoint is configured, 
contact closure puts the controller into local setpoint 1. When 
contact opens, the controller returns to former operation—local or 
remote setpoint—unless SP Select key is pressed while digital 
input is active. If this happens, the controller will stay in the local 
setpoint mode when contact opens. 
TO 2SP 
TO LOCAL SETPOINT TWO—Contact closure puts the controller 
into local setpoint 2. 
TO 3SP 
TO LOCAL SETPOINT THREE—Contact closure puts the 
controller into local setpoint 3.
TO DIR 
TO DIRECT ACTION—Contact closure selects direct controller 
action.
TO HOLD 
TO HOLD—Contact closure suspends Setpoint Program or 
Setpoint Ramp. When contact reopens, the controller starts from 
the Hold point of the Ramp/Program unless the Ramp/Program 
was not previously started via the 
Run
Hold
Run
Hold
Run
Hold
key. 
This selection applies to either loop. 
TO PID2 
TO PID2—Contact closure selects PID Set 2. 
PV 2IN 
PV=INPUT 2—Contact closure selects PV = Input 2.
RERUN
RERUN--Allows the Setpoint Programmer to be reset to the initial 
segment of its current cycle, unit stays in previous mode.