56  UDC3200 Universal Digital Controller Operator Manual  04/08 
Function
Prompt
Lower Display
Selections or
Range of Setting
Upper Display
Parameter
Definition
TRACK
OUTPUT TRACKS INPUT 2—Contact closure allows Output to 
track Input 2. While the switch is open, the output is in accordance 
with its pre-defined functionality. When the switch is closed, the 
output value (in percent) will track the Input 2 percent of range 
value. When the switch is reopened, the output will start at this last 
output value and normal PID action will then take over control. The 
transfer is bumpless.
TO RSP 
TO REMOTE SETPOINT—Contact closure selects the Remote 
setpoint.
RST FB 
EXTERNAL RESET FEEDBACK—Contact closure allows Input 2 
to override the internal reset value.
To PURGE 
TO PURGE—Contact closure forces the loop to Manual mode with 
the output set to the Output High Limit configuration. MAN lights 
and the Output value is shown on the lower display. Opening the 
switch has no effect.  
 ATTENTION  Does not apply to Three Position Step Control.
Lo FIRE 
LOW FIRE—Contact closure forces the loop to Manual mode with 
the output set to the Output Low Limit configuration. MAN lights 
and the Output value is shown on the lower display. Opening the 
switch has no effect.  
 ATTENTION  Does not apply to Three Position Step Control.
MAN LAT 
MANUAL LATCHING—Contact closure transition forces the loop 
to Manual mode. Opening the switch has no effect. If the 
MAN/AUTO key is pressed while the switch is closed, the loop will 
return to Automatic mode.
PV Hold 
PROCESS VARIABLE HOLD—when the switch is closed, PV is 
frozen at last value. When switch opens, PV resumes.
DIG 1COMB  DIGITAL INPUT 1 COMBINATION SELECTIONS —This selection 
allows the specified function to occur in addition to the one chosen 
for DIG IN 1.
DISABLE
DISABLE—Disables combination function.
+PID2 
PLUS PID2—Contact closure selects PID Set 2.
+TO DIR 
PLUS DIRECT ACTION—Contact closure selects direct controller 
action.
+TO SP2 
PLUS SETPOINT 2—Contact closure puts the controller into SP2.
+DIS AT 
PLUS DISABLE ADAPTIVE TUNE—Contact closure disables 
Accutune process. 
+TO SP1 
PLUS SETPOINT 1—Contact closure puts the controller into SP1. 
+RUN
PLUS RUN SETPOINT PROGRAM/RAMP—Contact closure 
starts SP Program/Ramp if enabled. 
DIG INP2 
Same selections 
as for Digital Inp 1 
DIGITAL INPUT 2 SELECTIONS
DIG2COMB
Same selections 
as Digital Input 1 
Combinations
DIGITAL INPUT 2 COMBINATIONS