Section 4 Programming
4-5
Communication Defaults for Zones
ZONE # 1st 2nd ZONE # 1st 2nd ZONE # 1st 2nd ZONE # 1st 2nd
1 01 00 27 12 00 53 08 00 79 04 00
2 02 00 28 13 00 54 09 00 80 05 00
3 03 00 29 14 00 55 10 00 81 06 00
4 04 00 30 15 00 56 11 00 82 07 00
5 05 00 31 01 00 57 12 00 83 08 00
6 06 00 32 02 00 58 13 00 84 09 00
7 07 00 33 03 00 59 14 00 85 10 00
8 08 00 34 04 00 60 15 00 86 11 00
9 09 00 35 05 00 61 01 00 87 00 00
10 10 00 36 06 00 62 02 00 88 00 00
11 11 00 37 07 00 63 03 00 89 00 00
12 12 00 38 08 00 64 04 00 90 00 00
13 13 00 39 09 00 65 05 00 91 00 00
14 14 00 40 10 00 66 06 00 92 (DURESS) 11 00
15 15 00 41 11 00 67 07 00 95 00 00
16 01 00 42 12 00 68 08 00 96 00 00
17 02 00 43 13 00 69 09 00 97 00 00
18 03 00 44 14 00 70 10 00 98 00 00
19 04 00 45 15 00 71 11 00 99 06 00
20 05 00 46 01 00 72 12 00 ALARM RST. 00 00
21 06 00 47 02 00 73 13 00 TROUBLE 00 00
22 07 00 48 03 00 74 14 00 TRBLE. RST 00 00
23 08 00 49 04 00 75 15 00 BYPASS 00 00
24 09 00 50 05 00 76 01 00 BYP. RST. 00 00
25 10 00 51 06 00 77 02 00
26 11 00 52 07 00 78 03 00
Zone Response Type Definitions
Each zone must be assigned a zone type, which defines
the way in which the system responds to faults in that
zone. There are three keypad-activated zones (panic
keys; see note) for each partition, a polling loop
supervision zone, and four RF supervisory zones, two
for each RF receiver installed. Zone types are defined
below.
Type 00: Zone Not Used
Program with this zone type if the zone is not used.
Type 01: Entry/Exit #1 Burglary
Provides entry delay whenever the zone is faulted and
the system is armed in the AWAY or STAY mode. When
the panel is armed in the INSTANT or MAXIMUM
mode, no entry delay is provided. Exit delay begins
whenever the control is armed, regardless of the arming
mode selected. These delays are programmable.
Assign this zone type to zones that are used for primary
entry to and exit from the facility.
Type 02: Entry/Exit #2 Burglary
Provides a secondary entry delay, if the system is
armed in the AWAY or STAY modes and the zone is
faulted. When the panel is armed in the INSTANT or
MAXIMUM mode, no entry delay is provided.
Secondary exit delay begins whenever the control is
armed, regardless of the arming mode selected. These
delays are programmable.
Assign this zone type to zones that are used for entry
and exit of the facility and require more time than the
primary entry and exit point. Delay times for this zone
type must be greater than those for zone type 01 (e.g., a
garage, loading dock, or basement door).
Type 03: Perimeter Burglary
Provides an instant alarm if the zone is faulted and the
system is armed in the AWAY, STAY, INSTANT, or
MAXIMUM mode.
Assign this zone type to all exterior door and window
zones.