Section 5 Data Field Descriptions
5-15
FIELD
TITLE and DATA ENTRIES EXPLANATION
2*14
Scheduling Report Codes Report
Codes (Second Digit)
Enter 00-15.
This field has eight two-digit entries as follows: Early Opening, Early
Closing, Late Opening, Late Closing, No Opening (late to open), No
Closing (late to close), Auto-Arm Failure, and Access Schedule Changed.
Enter the report code 01-15 for each type of report. Enter 00 for no report.
2*18
Enable GOTO for this Partition
(partition-specific)
0 = disable
1 = enable
If enabled, this partition can be accessed from another partitions keypad
using the GOTO command.
2*19
Use Partition Descriptor
0 = disable
1 = enable
If enabled, the normal keypad display will include a partition number and
four-digit descriptor.
2*20
Enable J7 Triggers for Partition
(partition-specific)
0 = disable
1 = enable
If enabled, the J7 triggers function for this partition.
2*21
Supervision Pulses for LRR
0 = disable
1 = enable
There are three entries in this field as follows: Fire, Burglary/Audible
Panic, Silent Panic/Duress.
If enabled, causes the control to send periodic short pulses on the J7 radio
triggers to the LRR. The LRR uses these pulses to determine that its
connection to the control is still intact.
Must be 1 for UL installations.
WWW.DIYALARMFORUM.COM