B-18
Table B-23.
A2996A PowerTrust UPS Specifications.
Description Specification
Electrical Specifications:
AC Line Input:
Rated Voltage 100-120/200-240 VAC 50/60 Hz (Auto-ranging)
Rated Current 14-12 Amps and 7-6 Amps
(20 Amp max. branch circuit overcurrent protection)
AC Output:
Output VAC
(On Line Power)
Same as line input power
Output VAC
(On Battery)
115 VAC or 2 30 VA C (+
10% on battery with full load)
at 50/60 Hz (+
3 Hz)
Rated Voltage &
Current
100-120/200-240 VAC at 50/60 Hz
13-10.2 Amps and 6.5-5.4 Amps Max
Supported Load
Crest Factor
<
2.8 Amps (A Peak to A rms)
Rated power VA 1.3 kVA max with a 0.5 to 1.0 power factor
Rated Power Watts 1300 Watts assuming a 1.0 power factor
Waveshape True sine wave with < 10% total harmonic distortion
(on a purely resistive load)
Transfer Time AC Failure - <
10 msec to switch to battery power
AC Restored -5 Second delay returning to phase lock to input AC
Phasing Phase locked to within 5º of input utility AC
Safety Agency Approvals UL, CSA, and TUV
Battery:
Type Maintenance-free, sealed, lead-acid type (10 Amp/Hour)
Nominal open
circuit voltage 60 VDC