Table 8: Enclosure 3-phase 2400 W power supply specifications (International)
Specification Value
Power cords (4) IEC-309 220–240 VAC, 5-pin, 16 A
3.0 m (10 ft)
Max input current per line cord 12.1 A at 220 VAC
11.1 A at 240 VAC
Output 2450 W per power supply
Input requirements
Rated input voltage 200–240 VAC line-to-neutral 3-phase
Rated input frequency 50-60 Hz
Maximum inrush current 100 A for 10 ms
Ground leakage current 3.5 mA
Power factor correction 0.98
Table 9: Enclosure power requirements
Power required (50–60 Hz) Watts VA
User expected maximum power
1
9065 9250
1
Typical maximum power or user expected maximum power (input power at the AC input expressed in
watts and volt-amps). This figure was developed with the absolute maximum configuration running
applications designed to draw the maximum power possible. It is highly unlikely that any real-world
application will result in this amount of power use for any significant time period.
Table 10: Enclosure PDU power options
Source/Circuit
type
Source voltage
(nominal)
Plug or connector
type
Power receptacle
required
Number of power
cords required
(per enclosure
leaving the rack)
3–phase 60 A 200–240 VAC line-
to-line (phase-to-
phase), 3–phase
50/60 Hz
IEC 309 60 A 3-
Pole, 4 wire, Blue,
3.6 m (11.8 ft)
power cord
IEC 309 60 A 3-
Pole, 4 wire, Blue
2
3–phase 32 A 220–240 VAC line-
to-neutral 3–phase
50/60 Hz
IEC 309 32 A 4-
Pole, 5 wire, Red,
3.6 m (11.8 ft)
power cord
IEC 309 32 A 4-
Pole, 5 wire, Red
2
Table Continued