Removal and replacement procedures 30
To replace the component, reverse the removal procedure.
48V DC power supply option
One of the following optional input cables with pre-fastened ring tongues may be purchased from Hewlett
Packard Enterprise or an authorized reseller:
A5S97A1.3-m (7.55-ft) 48V DC Power Cable Kit
A5S98A2.5-m (3.94-ft) 48V DC Power Cable Kit
If you are not using an optional input cable, use a Hewlett Packard Enterprise-approved 10 or 12 AWG
green and yellow ground cable, no shorter than 150 cm (59.06 in), and 10 or 12 AWG power cables.
CAUTION: Use only the ring terminals provided with the power supply for customer-built
power connections. Be sure no wire protrudes from the bottom of the ring terminal barrels.
To remove the component:
1. Make sure the 48V DC power source is off or the PDU breaker is in the off position, and then
disconnect the power cord from the 48V DC power source or PDU.
2. Remove the power cord from the cable management arm, if installed.