Removal and replacement procedures 40
2.
Install the access panel ("Access panel" on page 27).
3. Slide the server into the rack.
4. Power up the server.
Fan blank
Install fans 1 and 2 only when processor 2 is installed. When only one processor is installed, install the fan
blanks in bays 1 and 2 ("Fan modules" on page 84).
To remove the component:
1. Power down the server (on page 25).
2. Remove all power:
a. Disconnect each power cord from the power source.
b. Disconnect each power cord from the server.
3. Extend the server from the rack (on page 26).
4. Remove the access panel ("Access panel" on page 27).
5. Remove the fan blanks.
To replace the component, reverse the removal procedure.
Flash-backed write cache procedures
Two types of procedures are provided for the FBWC option:
Removal and replacement of failed components:
o Removing the cache module ("Cache module" on page 41)
o Removing the capacitor pack ("FBWC capacitor pack" on page 41)
Recovery of cached data from a failed server ("Recovering data from the flash-backed write cache"
on page 42)
CAUTION: Do not detach the cable that connects the battery pack or capacitor pack to the
cache module. Detaching the cable causes all data in the cache module to be lost.