60
system will not perform as well.
Nonraised floor installations If the computer room does not have a
raised floor, use a cable trough assembly to route equipment power
cables.
This cable trough assembly may be used as the conduit for high
frequency ground. In addition to possible ground connections to
Hewlett-Packard cabinets, the cable trough should be connected to the
electrical service ground at multiple connection points via a minimum #6
AWG (16mm2) wire ground conductor. See the figure following for
details.
Ground wire
to power panel
ding clamp
Band and pedestal Grounding braid
to computer equipment
Grounding grid eleme
Hex b
Floor panel