Equipment grounding implementation details
If it has been determined to be necessary, connect all Hewlett-Packard
equipment cabinets to the site ground grid as follows:
Attach one end of each ground strap to the applicable cabinet ground
lug.
Attach the other end to the nearest pedestal base (raised floor) or
cable trough ground point (nonraised floor).
Check that the braid contact on each end of the ground strap consists
of a terminal and connection hardware (a 1/4-in. (6.0-mm) bolt, nuts,
and washers).
Check that the braid contact connection points are free of paint or
other insulating material and treated with a contact enhancement