11. Make sure that the GPU is firmly seated in the slot.
12. Close the PCIe slot cover retainer.
13. Install the system air baffle on page 31.
14. Install the PCI air baffle on page 30.
15. Install the access panel on page 26.
16. Do one of the following:
Server in rack mode: Install the server into the rack on page 53.
Server in tower mode: Return the server to an upright position.
17. Connect all peripheral cables to the server.
18. Connect each power cord to the server.
19. Connect each power cord to the power source.
20. Power up the server on page 23.
The installation is complete.
Redundant fan option kit
The redundant fan option kit contains the redundant system and PCI fans. Mixed default fan + redundant fan
configuration in the same server is not supported.
Redundant fan mode is required to meet the system thermal requirements under the following conditions:
Server with the following options installed:
SFF hot-plug SAS SSD
SFF hot-plug SAS drives in box 2
The ambient temperature reaches 35°C (95°F) to 40°C (104°F).
Hardware options installation 81