Figure 5-97 Installing a fan module
Step 7 Wait about two minutes and check the status of the Running/Alarm indicator on the fan
module to determine whether the fan module is successfully installed. Figure 5-98 shows the
location of the Running/Alarm indicator.
l If the indicator is steady green, the fan module is successfully installed.
l If the indicator is steady red or off, the newly installed fan module is faulty, the fan
module slot is faulty, or the fan module is incorrectly installed.
Figure 5-98 Running/Alarm indicator on a fan module
Step 8 If the fan module is successfully installed, close the panel, as shown in Figure 5-99.
OceanStor Dorado V3 Series
Parts Replacement
5 Replacing FRUs
Issue 05 (2019-01-30) Copyright © Huawei Technologies Co., Ltd. 175