Parameter Description
Limitation mode ● Total power
● Single-phase power
● When this parameter is set to
Total power, no backfeeding
occurs on the three phases.
● When this parameter is set to
Single-phase power, no
backfeeding occurs on the phase
with the maximum power.
PV plant capacity N/A Species the total maximum active
power in the inverter cascading
scenario.
Maximum grid
feed-in power
(%)
N/A Species the percentage of the
maximum active power of the grid-
tied point to the PV plant capacity.
Power
adjustment
period
N/A Species the shortest interval for a
single export limitation adjustment.
Maximum
protection time
N/A ● Species the time for detecting
power meter data. If the Smart
Dongle does not detect any power
meter data within the preset time,
the Smart Dongle delivers the
preset value of the Fail-safe
power threshold to the inverter
for protection.
● The recommended value is 5s or
greater.
Power control
hysteresis
N/A Species the dead zone for adjusting
the inverter output power. If the
power uctuates within the power
control hysteresis, the power is not
adjusted.
Fail-safe power
threshold
N/A Species the derating value of the
inverter active power by percentage.
If the Smart Dongle does not detect
any power meter data or the
communication between the Smart
Dongle and the inverter is
disconnected, the Smart Dongle
delivers the derating value of the
inverter active power by percentage.
----End
FusionSolar Smart PV Management System
Connection
User Manual (Inverters + SDongleA) 5 Site Deployment and Commissioning
Issue 02 (2021-11-25) Copyright © Huawei Technologies Co., Ltd. 46