EasyManuals Logo

Huawei SUN2000-100KTL Series User Manual

Huawei SUN2000-100KTL Series
149 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #118 background imageLoading...
Page #118 background image
Alarm
ID
Alarm
Name
Alarm
Severit
y
Possible Causes Suggestions
2012 String
Current
Backfee
d
Warnin
g
Cause ID = 1–20: PV1–PV20
Only a few PV modules are
connected in series in the PV
string. Therefore, the terminal
voltage is lower than that of
other PV strings.
1. Check whether the number
of PV modules connected
in series in the PV string is
less than that in other PV
strings connected in
parallel. If yes, wait until
the solar irradiance
declines at night and the
PV string current drops
below 0.5 A. Then, turn
o
the DC switches and add
more PV modules.
2. Check whether the PV
string is shaded.
3. Check whether the open-
circuit voltage of the PV
string is normal.
SUN2000-(100KTL, 110KTL, 125KTL) Series
User Manual 8 Maintenance
Issue 07 (2020-09-15) Copyright © Huawei Technologies Co., Ltd. 110

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000-100KTL Series and is the answer not in the manual?

Huawei SUN2000-100KTL Series Specifications

General IconGeneral
BrandHuawei
ModelSUN2000-100KTL Series
CategoryInverter
LanguageEnglish

Related product manuals