Alarm
ID
Alarm
Name
Alarm
Severit
y
Possible Causes Suggestions
2038 Unstabl
e Grid
Frequen
cy
Major Cause ID = 1
Power grid exception: The actual
grid frequency change rate does
not comply with the local power
grid standard.
1. If the alarm occurs
occasionally, the power grid
may be abnormal temporarily.
The solar inverter
automatically recovers after
detecting that the power grid
becomes normal.
2. If the alarm occurs
frequently, check whether the
grid frequency is within the
acceptable range. If not,
contact the local power
operator.
2039 Output
Overcur
rent
Major Cause ID = 1
The power grid voltage drops
dramatically or the power grid is
short-circuited. As a result, the
solar inverter transient output
current exceeds the upper
threshold and therefore the solar
inverter protection is triggered.
1. The solar inverter detects
its external working
conditions in real time.
After the fault is rectied,
the solar inverter
automatically recovers.
2. If the alarm occurs
frequently and
aects the
energy yield of the PV
plant, check whether the
output is short-circuited. If
the fault cannot be
rectied, contact your
dealer or Huawei technical
support.
2040 Output
DC
Compon
ent
Overhig
h
Major Cause ID = 1
The DC component of the solar
inverter output current exceeds
the specied upper threshold.
1. If the exception is caused
by an external fault, the
solar inverter automatically
recovers after the fault is
rectied.
2. If the alarm occurs
frequently, contact your
dealer or Huawei technical
support.